IG-287-EN version 03; 24/07/2020
9
General Instructions
transforma
.plur: Transformers with corrugated tank
and submerged in dielectric liquid from 3150 kVA
Lifting, moving and handling
•
Transformers with eyebolts on the the tank cover
Whenever the lifting eyebolts are placed on the cover
because the weight of the transformer so allows, and
they are identified in yellow (Figure 2.9).
Figure 2.9.
Eyebolts on the the tank cover
In the case of transformers of lower weight, two or four
optional eyebolts are available on the cover.
In the case of transformers with four eyebolts
considerably far apart, four lifting hooks must be used
simultaneously.
In the case of transformers with two eyebolts, or four
eyebolts very close together, two hooks with the
suitable means can be used. (Figure 2.10).
Figure 2.10.
Position of the four eyebolts on the cover
Figure 2.11.
Position of the two eyebolts on the cover