background image

Manual version V1.0 Update 2021-08-26 

VC1 Series PLC Quick Start User Manual 

This quick start manual is to offer you a quick guide to the design, installation, connection and 
maintenance of VC1 series PLC, convenient for on-site reference. Briefly introduced in this 

booklet are the hardware specs, features, and usage of VC1 series PLC, plus the optional 

parts and FAQ for your reference. For more detailed product information, please refer to the 

user  manual  of  “VC  series  programing  manual”  and  “Autostudio  programming  software” 

issued by our company. If necessary, consult the supplier. You can also log in 

www.veichi.org

 

to download PLC related technical data or feed back PLC related problems on the website. 
1    Product Introduction 

1.1    Model designation 

The model designation is shown in the following figure. 

 

 

 

To Customers:   
Thank you for choosing our products. To improve the product and provide better service for 

you, could you please fill in the form after the product has been operated for 1 month, and 

mail or fax it to our Customer Service Center? We will send you an exquisite souvenir upon 

receiving the complete Product Quality Feedback Form. Furthermore, if you can give us some 

advices on improving the product and service quality, you will be awarded a special gift. Thank 

you very much! 
Veichi Electric Co., LTD. 

Product Quality Feedback Form 

Customer name 

 

Tele 

 

Address 

 

Zip code 

 

Model 

 

Date of use 

 

Machine SN 

 

Appearance or 
structure 

 

Performance 

 

Package 

 

Material 

 

Quality problem during 
usage 

 

Suggestion about 
improvement 

 

1.2    Outline 

The outline of the VC1 series module is shown in the following figure by taking the example 

of VC1-1614MAR. 

S G 4 8 5 -

X 0

X 2

X 4

X 6

X 1 0 X 1 2 X 1 4

4 8 5 +

S / S

X 1

X 3

X 5

X 7

X 1 1 X 1 3

X 1 5

2 4 V

Y 4

Y 6

Y 1 0 Y 1 2

C O M

Y 1

Y 3 C O M 1 Y 5

Y 7 C O M 2 Y 1 1 Y 1 3

Y 0

C O M 0

Y 1 5

Y 1 4

Y 2

V E I C H I

R U N

E R R

P W R

V C 1 - 1 6 1 4 M A R

O u t p u t   s i g n a l   s t a t u s   i n d i c a t o r

S y s t e m   w o r k i n g   s t a t u s   i n d i c a t o r

R i g h t   e x t e n s i o n   m o d u l e   i n t e r f a c e

I n p u t   s i g n a l   s t a t u s   i n d i c a t o r

O u t p u t   s i g n a l   t e r m i n a l

I n p u t   s i g n a l   t e r m i n a l

P o w e r   s u p p l y

R S - 4 8 5   I n t e r f a c e

U S B   I n t e r f a c e

M o d e   s e l e c t i o n   s w i t c h

S e r i a l   p o r t ( R S - 2 3 2 )

L e f t   e x t e n s i o n   m o d u l e   i n t e r f a c e

B a t t e r y   i n t e r f a c e

X 1 6

X 1 7

T e r m i n a l   r e s i s t a n c e ( 1 2 0 Ω )

 

PORT0 adopts the RS232, and the Mini DIN8 socket. 1 RS-485, USB interface is Type-C. The 

right extension module interface is used for extension module connection, the left extension 

module is used for communication module connection. RUN and STOP switched by MODE 

selection. Two RS-485 terminal resistor, the resistance is 120Ω. 

1.3    Terminal Introduction 

1

24 point module I/O points are shown below: 

Input terminal: 

 

Output terminal: 

 

2

30 point module I/O points are shown below: 

Input terminal: 

 

Output terminal: 

 

3.    Power supply 
The specification of PLC built-in power and power for extension modules is listed in the 

following table.   

Item 

Unit 

Min. 

Rated 

Max. 

Note 

Power supply voltage 

Vac 

85 

220 

264 

Normal startup and operation   

Input current   

1.5 

Input: 90Vac, 100% output   

Rated output 
current 

5V/GND 

mA 

1500 

The total power of outputs 5V/GND 
and 24V/GND ≤ 30W. 

24V/GND

 

mA 

1000 

24V/COM

 

mA 

 
3    Digital input and output characteristics 

3.1    Input Characteristic And Specification 

The input characteristic and specs are shown as follows: 

Item   

High-speed input terminals X0~X7 

General input terminal 

Sigal input type 

Source mode or sink mode, user set through “S/S” terminal 

Electric 
paramet
ers 

Input voltage  24Vdc 
Input 
impedance   

3.3KΩ 

4.3kΩ 

Input ON 

External circuit resistance < 400Ω 

External circuit resistance < 400Ω 

Input OFF 

External circuit resistance > 24KΩ 

External circuit resistance > 24KΩ 

Filtering 
function 

Digital filter 

X0~X7 have digital filtering function. Filtering time: 0~60ms setting by user 
programing. 

Hardware 
filter 

Input terminals other than X0 ~ X7 are of hardware filtering. Filtering time: about 
10ms 

High speed function 

X0~X7: high-speed counting, interrupt, and pulse catching   
X0 and X1: up to 50kHz counting frequency   
X2~X5: up to 10kHz counting frequency 
The sum of input frequency should be less than 60kHz 

Common terminal 

Only one common terminal: S/S 

 
The counter input port has a corresponding maximum frequency limit.. Any frequency higher 

than that may result in incorrect counting or abnormal system operation. Make sure that the 

input terminal arrangement is reasonable and external sensors used are proper. 
 
PLC provides a port "S/S" to select the input mode of the signal, which can be set to source 
input mode or sink input mode. Connect "S/S" to "

24V", that is, set to sink input mode, and 

NPN type sensor can be connected. 

 

 

Input connection example 

The  following  diagram  shows  an  example  of  VC1-1614MAR  in  connection  with  an  VC-

0808ENR, which realizes simple positioning control. The positioning signals from the PG are 

input through high speed counting terminals X0 and X1, the limit switch signals that require 

Reviews: