OPERATING INSTRUCTIONS

procedure will activate the Diesel-Burner and the indicator 

light located on the “Diesel” switch.  Allow 10-20 minutes for 

the Hydro-Hot System to reach operating temperature.  Please 

note that the Diesel-Burner is the 

primary heat source

 for 

heating both the interior and the domestic hot water (such as 

when cool ambient temperatures exist and/or when there is a 

high demand for domestic hot water).

Electric Heating Element:

Turn the “Electric” switch 

ON

reference Figure 2.  This  

procedure will activate the 120 Volt-AC Electric Heating  

Element and the indicator light located on the “Electric” 

switch.  Allow 1-2 hours for the Hydro-Hot System to reach  

operating temperature.

Also, please note that the Electric Heating Element is a  

secondary heat source

 for heating both the interior and the 

domestic hot water during low heating demand situations 

(such as when moderate ambient temperatures exist and/or 

when there is a low demand for domestic hot water).

The Hydro-Hot’s Exhaust is HOT!

DO NOT park in areas where dry conditions exist under-

neath the vehicle, as a fire may result (e.g., in a dry, grassy 

field)!

DO NOT operate the Hydro-Hot’s Diesel-Burner inside an 

enclosed building!

The Heater must be switched 

OFF

 when refueling.

DO NOT 

operate the Diesel-Burner and/or Electric Heating 

Element without the antifreeze and water heating solution in 

the Hydro-Hot’s Boiler Tank.  Failure to do so will cause 

seri-

ous damage

 to the Heater.

Activating the Hydro-Hot Heating System:

Diesel-Burner:

Turn the “Diesel” switch 

ON

; reference Figure 2.  This  

FONCTIONNEMENT

démarrer le brûleur diesel et allumer le voyant situé sur 

l’interrupteur Diesel. Attendez de 10 à 20 minutes pour que le 

système Hydro-Hot atteigne sa température de fonctionnement. 

Notez que le brûleur diesel est la 

source de chaleur principale

 

pour chauffer l’intérieur et l’eau domestique (lorsque la 

température ambiante est basse ou lorsqu’il y a une demande 

importante d’eau chaude domestique).

Élément de chauffage électrique :

Mettez le commutateur Electric à 

ON

 : voir figure 2. Ceci 

va allumer l’élément de chauffage électrique à 120 Vca et 

le voyant situé sur l’interrupteur Electric. Attendre de 1 à 2 

heures pour que le système Hydro-Hot atteigne sa température 

de fonctionnement.

Notez que l’élément de chauffage électrique est la 

source 

secondaire de chaleur

 pour chauffer l’intérieur et l’eau 

domestique (lorsque la température ambiante est moyenne ou 

lorsqu’il y a une demande faible d’eau chaude domestique).

La sortie des gaz du tuyau d’échappement du Hydronic 

Hydro-Hot est TRÈS CHAUDE !

NE PAS garer le véhicule dans un endroit herbeux asséché 

où un incendie pourrait se produire (ex.: pré asséché) !

NE PAS faire fonctionner le brûleur diesel du Hydronic 

Hydro-Hot à l’intérieur d’un bâtiment fermé.

Le brûleur doit être éteint durant les ravitaillements en 

carburant.

NE PAS 

faire fonctionner le brûleur diesel ou l’élément de 

chauffage sans solution de chauffage d’antigel et d’eau dans la 

chaudière du Hydro-Hot. À défaut de se conformer, le système 

de chauffage pourrait être 

sérieusement endommagé

.

Démarrage du système de chauffage Hydro-Hot :

Brûleur diesel :

Mettez l’interrupteur Diesel à 

ON

; voir figure 2. Ceci va 

Summary of Contents for Hydro-Hot H2E-200-01E

Page 1: ...Owner s Manual Manuel du propri taire H2E 200 01E...

Page 2: ...ease Mail To Vehicle Systems Warranty Department 15549 East Highway 52 Ft Lupton CO 80621 Nom du propri taire __________________________________________________ Adresse _______________________________...

Page 3: ...Vehicle Systems Inc Warranty Department 15549 East Highway 52 Ft Lupton CO 80621 Vehicle Systems Inc Warranty Department 15549 East Highway 52 Ft Lupton CO 80621...

Page 4: ...ge 7 Maintenance Maintenance Schedule Page 9 Winterization Domestic Hot Water System Page 11 Table of Contents continued on following page TABLE DES MATI RES Information sur la garantie D claration de...

Page 5: ...ating Solution Appropriate Water Propylene Glycol Solution Mixture Ratio Page A1 Selecting an Appropriate Propylene Glycol Based Antifreeze Page A4 TABLE DES MATI RES D pannage Information g n rale pa...

Page 6: ...o 5 00 PM Mountain Standard Time INFORMATION SUR LA GARANTIE Garantie limit e de trois 3 ans sur le syst me de chauffage Hydronic Hydro Hot H2E 200 01E Vehicle Systems Inc garantie que le bo tier de l...

Page 7: ...ppendix A contact Vehicle Systems Technical Support Department at 1 800 685 4298 or visit the website at www vehiclesys com INTRODUCTION Ce manuel devrait tre gard en bon tat dans un endroit s r et fa...

Page 8: ...For more information call Vehicle Systems Inc 1 800 685 4298 Figure 1 INTRODUCTION INTERRUPTEUR FLOTTEUR INTERRUPTEUR DE VERROUILLAGE PLAQUE DE SIGNAL TIQUE CONNEXION DU VASE D EXPANSION THERMOSTATS D...

Page 9: ...use seri ous damage to the Heater Activating the Hydro Hot Heating System Diesel Burner Turn the Diesel switch ON reference Figure 2 This FONCTIONNEMENT d marrer le br leur diesel et allumer le voyant...

Page 10: ...demand for continuous domestic hot water ceases the Hydro Hot will enable the fans and pumps to Note continued on next page FONCTIONNEMENT NOTE Le br leur diesel et l l ment de chauffage lectrique son...

Page 11: ...n feature reduces the total operating hours of the Diesel Burner and the Electric Heating Element Diesel Electric Engine Preheat Indicator Light Figure 2 NOTE suite de chauffage Notez que le voyant d...

Page 12: ...l switch Electric Heating Element is activated by the Electric switch The Boiler Tank heats the antifreeze and water heating solution to 190 F FONCTIONNEMENT Sch ma de fonctionnement du Hydronic Hydro...

Page 13: ...ned Continuous hot water is supplied to the faucet Hydro Hot Operational Flow Chart continued OPERATING INSTRUCTIONS Un thermostat de zone demande de la chaleur La solution de chauffage d antigel et d...

Page 14: ...Hot s Boiler Tank Failure to do so will cause serious damage to the Heater To keep the Hydro Hot running smoothly it is ideal to have ENTRETIEN Calendrier d entretien Lorsque le Hydro Hot est sa temp...

Page 15: ...n Air adjustment MAINTENANCE Fuel Filter 10 Micron Combustion Chamber Fuel Nozzle 0 35 GPH Figure 3 chaque ann e pour garder le Hydro Hot en bon tat de fonctionnement Cette mise au point devrait compr...

Page 16: ...s one at a time until only clear water is present visible Reference Figure 4 HIVERISATION Des dommages s rieux seront caus s au syst me d eau chaude domestique du Hydro Hot lors de temp ratures sous l...

Page 17: ...ing to them at the following address Recreation Vehicle Industry Association 1896 Preston White Drive P O Box 2999 Reston VA 20195 0999 WINTERIZATION HIVERISATION Si vous d sinfectez le syst me d eau...

Page 18: ...nto a container of RV Antifreeze and allow this to pump through the Domestic Water System until the faucets run pure antifreeze Figure 4 HIVERISATION VUE DE DESSUS Vers les robinets d eau chaude SORTI...

Page 19: ...tus Overload Fault Pump 2 Pump 1 Pump 3 Diesel Burner Status Heating Zones Status ELECTRONIC CONTROLLER Figure 5 D PANNAGE Information g n rale Si le br leur diesel venait tomber en panne faites les v...

Page 20: ...ngers i e fan motors If any of Voyant Low Tank Level Cutoff Interrupteur de bas niveau dans la chaudi re Ce voyant s allumera en ROUGE si l l ment de chauffage lectrique 120 Vca s est teint ou si le b...

Page 21: ...re to heat the motorhome domestic hot water simply choose the desired heat source s and leave the switch s i e Diesel and or Electric ON indique qu il y a une surcharge lectrique court circuit sur le...

Page 22: ...do not attempt a Heater restart contact Vehicle Systems Technical Support Department at 1 800 685 4298 for assistance Voyant Electric Heating Element Status tat de l l ment de chauffage lectrique Ce v...

Page 23: ...Systems Technical Support Department at 1 800 685 4298 D PANNAGE Tableau d interpr tation des s quences des voyants de panne clignotants 1x Le contr le du br leur diesel ne re oit pas un minimum de 11...

Page 24: ...Antifreeze and Water Heating Solution APPENDIX A Solution de chauffage d antigel et d eau Annexe A...

Page 25: ...ansport the heat created from the internal process throughout the motorhome where it can be utilized productively rather than dissipating due to its change from a liquid to a gas Annexe A Solution de...

Page 26: ...f antifreeze to water and how it directly affects the solution s freezing point APPENDIX A ANTIFREEZE AND WATER HEATING SOLUTION Inhibiteur de corrosion Une autre fonction importante de l antigel est...

Page 27: ...0 20 40 60 20 30 10 20 30 40 50 60 Freezing Point Temperature In Degrees Fahrenheit l o c y l G e n e l y p o r P f o e g a t n e c r e P n o i t u l o S n i 28 7 8 19 26 Annexe A Solution de chauffa...

Page 28: ...eir potentially hazardous properties they should never be used in the Hydro Hot s Hydronic Heat ing System APPENDIX A ANTIFREEZE AND WATER HEATING SOLUTION Choix de l antigel appropri base de propyl n...

Page 29: ...System Owner s Manual Manuel du propri taire du syst me de chauffage Hydronic Hydro Hot 09 05 Date Service Performed Service Center OWNER S SERVICE LOG Date Entretien ex cut Centre de service JOURNAL...

Page 30: ...wner s Manual Manuel du propri taire du syst me de chauffage Hydronic Hydro Hot 09 05 Date Service Performed Service Center OWNER S SERVICE LOG Continued Date Entretien ex cut Centre de service JOURNA...

Page 31: ...15549 East Highway 52 Fort Lupton Colorado 80621 1 800 685 4298 Fax 303 857 9000 Copyright 2005 Vehicle Systems Inc All rights reserved www vehiclesys com...

Reviews: