background image

3

-

step switch for mode adjustment of the second output relay

.

T

he

individual switch positions are assigned as follows

:

 2 

  3 

 4 

 5 

 6 

 7 

 8

O

N

3

1

3362

CH1 output parallel

CH2 output separate

CH1 with alarm

F

ig

.

16

:

S

lide switch for adjustment of the relay outputs

(

D

)

l

CH

1

output parallel

-

B

oth relay outputs switch in parallel

.

T

he

second relay

(

15

-

17

)

switches analogue to relay

1

(

4

-

6

)

l

CH

2

output separate

-

T

wo

-

point control or two independent relay

outputs

.

T

he second relay

(

15

-

17

)

switches independently of

relay

1

(

4

-

6

)

l

CH

1

with alarm

-

F

ault signal with relay output

2

.

T

he second relay

(

4

-

6

)

triggers a fault signal

.

3

-

step switch for adjustment of the switching delay

.

T

he adjusted

switching delay applies to the switch on and switch o

delay

.

O

N

3

1

3362

6 s

3 s

0,5 s

 2 

  3 

 4 

 5 

 6 

 7 

 8

F

ig

.

17

:

S

lide switch for setting the switching delay

(

E

)

l

6

s

l

3

s

l

0

.

5

s

S

lide switch for adjust

-

ment of the relay out

-

puts

(

D

)

S

lide switch for setting

the switching delay

(

E

)

22

VEGATOR

632

S

ignal conditioning instrument

6

A

djustment elements

35243

-

EN

-

120228

Summary of Contents for VEGATOR 632

Page 1: ...Operating Instructions VEGATOR 632 Signal conditioning instrument Document ID 35243 Signal conditioning instruments and communication...

Page 2: ...lation 10 5 Connecting to power supply 5 1 Preparing the connection 12 5 2 Connection procedure 13 5 3 Wiring plan 13 6 Adjustment elements 6 1 Adjustment elements Overview 19 7 Set up Single channel...

Page 3: ...1 3 Two point control 46 11 4 Four channel operation 48 11 5 Two point control and two channel operation 49 12 Maintenance and fault recti cation 12 1 Maintaining 50 12 2 Remove interferences 50 12 3...

Page 4: ...practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warni...

Page 5: ...cturer Arbitrary conversions or modi cations are explicitly forbidden 2 3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application speci c hazards e g vessel...

Page 6: ...erating instructions manual and come with the Ex approved instruments 2 7 Environmental instructions Protection of the environment is one of our most important duties That is why we have introduced an...

Page 7: ...r identi cation and use of the instrument l Article number l Serial number l Technical data l Article numbers documentation l Information about connection and adjustment of the instrument The serial n...

Page 8: ...ping and the mode can be adjusted on the signal conditioning instrument via the slide switch The instrument function can be preadjusted with a DIL switch block The switching point can be adjusted with...

Page 9: ...llowing conditions l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration l Storage and transport temperat...

Page 10: ...oisture protected mounting outside the switching cabinet we o er an insulated protective housing with transparent cover IP 65 for surface mounting 4 2 Instructions for installation A VEGATOR 632 in Ex...

Page 11: ...instrument in the following sequence 1 Switch o power supply 1 2 b b a a Fig 4 Dismounting of the signal conditioning instrument 2 Remove the terminal blocks with a screwdriver 3 Open the slide with...

Page 12: ...61326 for industrial areas screened cable should be used If screened cable is necessary connect the cable screen on both ends to ground potential In the sensor the screen must be connected directly t...

Page 13: ...Connect power supply switched o to terminal 1 and 2 The electrical connection is nished 5 3 Wiring plan Note In conductive vessels the ground cable has contact to the grounded vessel via the process...

Page 14: ...the additional electronics for line break monitoring 1 Connection to terminal 1 ground rod longest rod 2 Connection to terminal 2 max rod shortest rod 3 Additional electronics for line break monitorin...

Page 15: ...Level detection in metallic conductive vessels 1 Ground 2 max channel 1 CH 1 3 Level relay 1 4 Level relay 2 or fail safe relay 5 Voltage supply 6 Probe e g EL1 You can nd detailed information under S...

Page 16: ...tive vessels 1 Ground 2 max channel 1 CH 1 3 Level relay 1 4 Level relay 2 or fail safe relay 5 Voltage supply 6 Probe e g EL3 You can nd detailed information under Set up Single point control as well...

Page 17: ...1 Ground 2 max channel 1 CH 1 3 min channel 2 CH 2 4 Level relay 1 5 Level relay 2 or fail safe relay 6 Voltage supply 7 Probe e g EL3 You can nd detailed information under Set up Two point control as...

Page 18: ...Ground 2 max channel 1 CH 1 3 min channel 2 CH 2 4 min channel 2 CH 2 5 max channel 1 CH 1 6 Level relay 1 7 Level relay 2 or fail safe relay 8 Voltage supply 9 Probe e g EL3 A Min max control signal...

Page 19: ...2 3 4 5 6 7 8 calibration CH1 CH2 17 min max 3 1 3362 C B A D E Fig 12 VEGATOR 632 Adjustment elements A DIL switch block B Potentiometer for switching point adjustment C Control lamps D Slid switch f...

Page 20: ...o 200 k l A4 Two point control l A5 Mode Channel 1 CH 1 o Max detection or over ow protection on Min detection or dry run detection l A6 Mode Channel 2 CH 2 o Max detection or over ow protection on Mi...

Page 21: ...ltage green gn 2 Control lamp Fault signal red rd 3 Control lamp Switching status channel 2 yellow ye 4 Control lamp Switching status channel 1 yellow ye l Green gn Operating control lamp Mains voltag...

Page 22: ...or two independent relay outputs The second relay 15 17 switches independently of relay 1 4 6 l CH 1 with alarm Fault signal with relay output 2 The second relay 4 6 triggers a fault signal 3 step sw...

Page 23: ...lay output 2 The following charts provide an overview of the relay switching conditions and the control lamps depending on the adjusted mode and level Level detection with one switching point l Min dr...

Page 24: ...ction or mac over ll protection l Channel 1 switching relay and channel 2 fail safe relay CH 1 with alarm Mode Level Channel 1 Channel 2 Control lamps max 6 4 5 16 17 15 ye ye gn rd max 6 4 5 16 17 15...

Page 25: ...relay output switches and the yellow control lamp changes condition 4 Turn the potentiometer approximately 15 in the same direction 5 If the relay output does not change you have to switch to the next...

Page 26: ...you have to switch to the next range 1 k If the relay output has switched empty the vessel until the electrode is uncovered The relay output must now switch again Adjustment in liquids with resistance...

Page 27: ...ching delay The adjusted switching delay refers to the switching function of the relay and applies only to the switch on delay Note When carrying out switching point adjustments keep in mind that ther...

Page 28: ...A with switch 7 for activation of the line break monitoring alarm You nd detailed information on how to trigger a fault signal via the second relay output in the previous chapter Adjust relay functio...

Page 29: ...ode and level Output relay 2 operates like output relay 1 The function of the two output relays is the same Switching condition of the two channels see CH 2 output separate Two point control pump cont...

Page 30: ...DIL switch block A switch 5 and 6 to on l Channel 1 relay 1 and channel 2 relay 2 switch separately CH 2 output separate l Two point control pump control DIL switch block A switch 4 to on s Mode Leve...

Page 31: ...ng to the following illustration 1 K 10 K 200 K 200 K CH1 CH2 max max off on 1 2 3 4 5 6 7 Fig 95 Conductive liquids up to 200 k 2 Turn potentiometer B to complete left position 3 Turn potentiometer B...

Page 32: ...ay output switches and the yellow control lamp changes condition 4 Turn the potentiometer approximately 15 in the same direction 5 If the relay output does not change you have to switch to the next ra...

Page 33: ...vered The relay output must now switch again Note A failure exists if the relay output does not switch over even in the last range You will nd instructions for fault recti cation in chapter Maintenanc...

Page 34: ...case of failure If you are using a probe without line break monitoring a fault signal will be triggered In this case set the switch 7 to o Only failures of channel 1 are monitored A failure is signall...

Page 35: ...the adjusted mode and level Output relay 2 operates like output relay 1 The function of the two output relays is the same Switching reaction of the two channels see CH 2 output separate Not useful for...

Page 36: ...l 2 relay 2 switch separately CH 2 output separate l Two channel control two separate switching points DIL switch block A switch 4 to o Mode Level Channel 1 Channel 2 Control lamps min max 6 4 5 16 17...

Page 37: ...he relay output switches and the yellow control lamp changes condition 4 Turn the potentiometer approximately 15 in the same direction 5 If the relay output does not change you have to switch to the n...

Page 38: ...utput does not change you have to switch to the next range If the relay output has switched empty the vessel until the electrode is uncovered The relay output must now switch again Adjustment in liqui...

Page 39: ...g the switching delay The adjusted switching delay refers to the switching function of the relay and applies only to the switch on delay Note When carrying out switching point adjustments keep in mind...

Page 40: ...itch block A with switch 7 for activation of the line break monitoring alarm You nd detailed information on how to trigger a fault signal via the second relay output in the previous chapter Adjust rel...

Page 41: ...ust switching delay See single channel two point or two channel control 10 5 Activate line break monitoring The line break monitoring or alarm function de nes the function of the instrument in case of...

Page 42: ...To ensure that the two VEGATOR 632 can synchronize their phases a connection cable is required between the two signal conditioning instruments Connect this connection cable according to the following...

Page 43: ...17 1 2 15 16 7 8 9 10 CH2 CH1 Master Slave 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON Fig 132 Level detection Single channel operation without alarm monitoring with ground electrode 1 Ground 2...

Page 44: ...CH1 Master Slave 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON 6 Fig 133 Level detection Single channel operation with alarm monitoring 1 Ground 2 max channel 1 CH 1 3 Level relay 4 Level relay or...

Page 45: ...15 16 7 8 9 10 CH2 CH1 Master Slave 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON Fig 134 Level detection Two channel operation outputs separate 1 Ground 2 max channel 2 CH 2 3 min channel 1 CH 1 4...

Page 46: ...5 16 7 8 9 10 CH2 CH1 Master Slave 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON 7 Fig 135 Two point control s with alarm monitoring 1 Ground 2 max channel 2 CH 2 3 min channel 1 CH 1 4 Level relay...

Page 47: ...L N L 4 5 6 17 1 2 15 16 7 8 9 10 CH2 CH1 Master Slave 4 5 6 17 TOR 149A ON Fig 136 Two point control s without alarm monitoring outputs parallel 1 Ground 2 max channel 2 CH 2 3 min channel 1 CH 1 4 L...

Page 48: ...6 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON L1 L N L 7 8 9 10 4 5 6 17 1 2 15 16 CH2 CH1 Master Slave 6 8 7 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON L1 L N L 7 8 9 10 4 5 6 17 1 2 15 16 CH2 CH1 M...

Page 49: ...49A ON L1 L N L 7 8 9 10 4 5 6 17 1 2 15 16 CH2 CH1 Master Slave 6 8 7 1 2 15 16 4 5 6 17 7 8 9 10 4 5 6 17 TOR 149A ON L1 L N L 7 8 9 10 4 5 6 17 1 2 15 16 CH2 CH1 Master Slave 6 8 7 Fig 138 Two poin...

Page 50: ...ge only the standard telephone costs will be charged The red failure control lamp LED of the signal conditioning instrument lights l Sensor not connected correctly Check the electrical connection by m...

Page 51: ...ing function of the signal conditioning instrument l Wrong setting of the change over switch for the level signal Set the change over switch for the level signal correctly See chapter Adjustment 12 3...

Page 52: ...he signal conditioning instrument 12 4 Instrument repair If a repair is necessary please proceed as follows You can download a return form 23 KB from our homepage at www vega com under Downloads Forms...

Page 53: ...the WEEE directive 2002 96 EG and the respective national laws Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points These may be used only...

Page 54: ...1 200 k adjustable Measuring circuit max 5 V e max 1 mA Permissible line capacitance 1 x 100 nF or 2 x 70 nF with min max control Switching hysteresis 15 Relating to the conductivity of the medium Adj...

Page 55: ...hanical data Screw terminals for wire cross section up to 1 5 mm AWG 16 Electrical protective measures Protection rating IP 20 Overvoltage category II Protection class II Electrical separating measure...

Page 56: ...14 2 Dimensions 108 mm 4 25 95 mm 3 74 22 5 mm 0 89 112 mm 4 41 Fig 141 Dimensions VEGATOR 632 56 VEGATOR 632 Signal conditioning instrument 14 Supplement 35243 EN 120228...

Page 57: ...VEGATOR 632 Signal conditioning instrument 57 14 Supplement 35243 EN 120228...

Page 58: ...58 VEGATOR 632 Signal conditioning instrument 14 Supplement 35243 EN 120228...

Page 59: ...VEGATOR 632 Signal conditioning instrument 59 14 Supplement 35243 EN 120228...

Page 60: ...vega com Printing date ISO 9001 All statements concerning scope of delivery application practical use and operating conditions of the sensors and processing systems correspond to the information avail...

Reviews: