Breaking capacity
1)
min. 50 mW, max. 500 VA, max. 54 W DC
Phase angle cos φ with AC
≥ 0.7
Switch-on/Switch-off delay
Ʋ
Basic delay
150 ms, ± 20 %
Ʋ
Adjustable delay
2/6/8 s, ± 20 %
Indicators
LED displays
Ʋ
Status, operating voltage
1 x LED green
Ʋ
Status, fault signal
1 x LED red
Ʋ
Status, operating relay
1 x LED yellow
Adjustment
7 x DIL switch
Setting mode, switching delay, function control, configu
-
ration second optional relay
Test key
for function test
Ambient conditions
Ambient temperature at the installation
site of the instrument
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature
-40 … +70 °C (-40 … +158 °F)
Relative humidity
< 96 %
Mechanical environmental conditions
Vibrations (oscillations)
Class 4M4 acc. to IEC 60721-3-4 (1 g, 4 … 200 Hz)
Impacts (mechanical shock)
Class 6M4 acc. to IEC 60721-3-6 (10 g/11 ms,
30 g/6 ms, 50 g/2.3 ms)
Electrical protective measures
Protection rating
IP 20
Overvoltage category (IEC 61010-1)
Ʋ
up to 2000 m (6562 ft) above sea level II
Ʋ
up to 5000 m (16404 ft) above sea
level
II - Only with connected overvoltage protection
Ʋ
up to 5000 m (16404 ft) above sea
level
I
Protection class
II
Pollution degree
2
Measures for electrical separation
Reliable separation according to VDE 0106 part 1 between all circuits
Ʋ
Reference voltage
253 V
1)
If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be
permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.