3 Mounting
VEGAPULS 61 • Profibus PA
47106-EN-161104
3 Mounting
3.1 Collar or adapter flange
For mounting the instrument on a socket, a combi compression flange
for DN 80 (ASME 3" or JIS 80) is also available for retro fitting. Option-
ally, the instrument can be also equipped with an adapter flange from
DN 100 (ASME 4" or JIS 100).
With the housing versions plastic, aluminium single chamber and
stainless steel, the collar flange can be placed directly over the hous-
ing. With the aluminium double chamber housing, retroactive mount-
ing in this way is not possible - the mounting type must be specified
with the order.
You can find drawings of these mounting options in chapter "
Dimen-
sions
".
Fig. 2: Flange mounting of the radar sensor
3.2 Mounting preparations, mounting strap
The mounting strap enables simple mounting on the vessel wall or
silo top. It is suitable for wall, ceiling or boom mounting. Especially in
open vessels this is a very easy and effective way to align the sensor
to the bulk solid surface.
The strap is supplied unassembled and must be screwed to the
sensor before setup with three hexagon socket screws M5 x 10 and
spring washers. Max. torque, see chapter "
Technical data
". Required
tools: Allen wrench size 4.
There are two ways to screw the strap onto the sensor. Depending
on the selected version, the sensors can be swivelled in the strap as
follows:
•
Single chamber housing