6
.
4
S
etup steps
A
fter
VEGAFLEX
67
is connected to voltage supply or after voltage
recurrence
,
the instrument carries out a self
-
check for approx
.
30
seconds
.
T
he following steps are carried out
:
l
I
nternal check of the electronics
l
I
ndication of the instrument type
,
the
fi
rmware as well as the
sensor
TAG
s
(
sensor designation
)
l
S
tatus byte goes brie
fl
y to fault value
T
hen the current measured value will be displayed and the
corresponding digital output signal will be outputted to the cable
.
1
)
B
efore starting the actual parameter adjustment of a
P
ro
fi
bus
PA
sensor
,
the address setting must
fi
rst be carried out
.
Y
ou will
fi
nd a
detailed description in the operating instructions manual of the
indicating and adjustment module or in the online help of
PACT
ware or
DTM
.
A
s
VEGAFLEX
67
is a distance measuring instrument
,
the distance
from the sensor to the product surface is measured
.
T
o have the real
product level displayed
,
an allocation of the measured distance to the
percentage height must be made
.
T
o carry out this adjustment
,
the
distance is entered with full and empty vessel
.
I
f these values are not
known
,
an adjustment with the distance values
,
e
.
g
.
10
%
and
90
%
is
also possible
.
S
tarting point for these distance speci
fi
cations is always
the seal surface of the thread or
fl
ange
.
W
ith these settings
,
the real
level is calculated
.
F
urthermore the operating range of the sensor is
limited from maximum to the required range
.
T
he real product level during this adjustment is not important
,
because
the min
./
max
.
adjustment is always carried out without changing the
product level
.
T
hese settings can be made ahead of time without the
instrument having to be installed
.
I
n the main menu item
"
B
asic adjustment
"
,
the individual submenu
items should be selected one after the other and provided with the
correct parameter values
.
S
tart your parameter adjustment with the following menu items of the
basic adjustment
:
P
roceed as follows
:
1
M
ove from the measured value display to the main menu by
pushing
[
OK
]
.
1
)
T
he values correspond to the actual measured level as well as to the set
-
tings already carried out
,
e
.
g
.
default setting
.
S
witch
-
on phase
A
ddress setting
P
arameter adjustment
C
arry out min
.
adjust
-
ment
VEGAFLEX
67
•
P
ro
fi
bus
PA
25
6
S
et up with the indicating and adjustment module
PLICSCOM
32313
-
EN
-
120329