3

A

djustment

T

he probe can be adapted to the dielectric constant of the

product directly on the electronics module

.

A

switching command can be triggered when the probe is

covered or laid bare

.

O

n the electronics module you will

nd the following indicating

and adjustment elements

:

l

S

ignal lamp for indication of the device status

.

3

.

4

S

torage and transport

Y

our instrument was protected by packaging during transport

.

I

ts capacity to handle normal loads during transport is assured

by a test acc

.

to

DIN

55439

.

T

he packaging of standard instruments consists of environ

-

ment

-

friendly

,

recyclable cardboard

.

F

or special versions

,

PE

foam or

PE

foil is also used

.

D

ispose of the packaging material

via specialised recycling companies

.

l

S

torage and transport temperature see

"

S

upplement

-

T

echnical data

-

A

mbient conditions

"

l

R

elative humidity

20

85

%

P

ackaging

S

torage and transport tem

-

perature

10

VEGACAP

62

-

with two

-

wire output

P

roduct description

30007

-

EN

-

060222

Summary of Contents for vegacap 62

Page 1: ...Operating Instructions VEGACAP 62 with two wire output...

Page 2: ...of operation 8 3 3 Adjustment 10 3 4 Storage and transport 10 4 Mounting 4 1 General instructions 11 4 2 Mounting information 12 5 Connecting to power supply 5 1 Preparing the connection 15 5 2 Connec...

Page 3: ...Dismounting 8 1 Dismounting procedure 26 8 2 Disposal 26 9 Supplement 9 1 Technical data 27 9 2 Dimensions 31 9 3 Industrial property rights 34 VEGACAP 62 with two wire output 3 Contents 30007 EN 0602...

Page 4: ...ymbolism used Information tip note This symbol indicates helpful additional information Caution warning danger This symbol informs you of a dangerous situation that could occur Ignoring this cautionar...

Page 5: ...peci c hazards e g vessel over ll or damage to system components through incorrect mounting or adjustment 2 4 General safety instructions VEGACAP 62 is a high tech instrument requiring the strict obse...

Page 6: ...nt temperature during operation is 110 C 230 F Measures for maintaining explosion protection during oper ation l Operate the instrument in the range of the speci ed electrical limit values Permissible...

Page 7: ...uirements acc to DIN EN 60079 14 2 8 Environmental instructions Protection of the environment is one of our most important duties That is why we have introduced an environment management system with t...

Page 8: ...th electrode 1 2 3 Fig 1 VEGACAP 62 with plastic housing 1 Housing cover 2 Housing with electronics 3 Process tting 3 2 Principle of operation VEGACAP 62 is a level sensor with partly insulated capaci...

Page 9: ...e of the electrode surfaces 3 Type of dielectric between the electrodes The probe and the vessel wall are the capacitor plates The measured product is the dielectric Due to the higher dielectric const...

Page 10: ...protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test acc to DIN 55439 The packaging of standard instruments consists of environ ment frien...

Page 11: ...ading the connection cable down ward in front of the cable entry Rain and condensation water can thus drain o This applies mainly to mounting outdoors in areas where moisture is expected e g by cleani...

Page 12: ...he probe of VEGACAP 62 to vibrate in resonance If a longer rod version is necessary you can secure the probe by fastening a suitable insulating brace or guy directly above the end of the rod If VEGACA...

Page 13: ...the vessel We recommend selecting an installation location where the probe detects the average value of the material cone The measuring probe must be mounted in a way that takes the arrangement of th...

Page 14: ...d d 6 1 2 3 Fig 6 Filling in the center emptying laterally 1 VEGACAP 62 2 Emptying opening 3 Filling opening 14 VEGACAP 62 with two wire output Mounting 30007 EN 060222...

Page 15: ...e data for power supply are stated in the Technical data in the Supplement VEGACAP 62 is connected with standard cable with round wire cross section An outer cable diameter of 5 9 mm 0 2 0 35 in ensur...

Page 16: ...to the open terminals according to the wiring plan 7 Press down the opening levers of the terminals you will hear the terminal spring closing 8 Check the hold of the wires in the terminals by lightly...

Page 17: ...DIL switch for measuring range selection 2 Ground terminal 3 Terminals 4 Control lamp For connection to a signal conditioning instrument The sensor is powered by the connected signal conditioning ins...

Page 18: ...g plans version IP 66 IP 68 1 bar 1 2 Fig 11 Wire assignment connection cable 1 br and bl for power supply or to the processing system 2 Screen 5 5 Start up reaction After connecting to voltage supply...

Page 19: ...10 I mA 20 5 2 3 1 5 3 4 5 t s 1 Fig 12 Start up reaction 1 Measured value VEGACAP 62 with two wire output 19 Connecting to power supply 30007 EN 060222...

Page 20: ...instrument before starting setup VEGACAP 62 The switching output will change if you set the mode switch afterwards This could possibly trigger other connected instruments or devices 6 2 Adjustment ele...

Page 21: ...in the vessel This is necessary so that the level switch can also reliably detect products e g with very low or very high dielectric value Range 1 0 20 pF Range 2 0 85 pF Range 3 0 450 pF Signal lamp...

Page 22: ...e world wide the support is only available in the English language The service is free of charge only the standard telephone costs will be charged VEGACAP 62 signals covered when the vibrating element...

Page 23: ...of VEGACAP 62 has detected a failure Exchange instrument or return it for repair 7 3 Exchange of the electronics module In general all oscillators of series CP60 can be interchanged If you want to use...

Page 24: ...ge Otherwise the plug may be in a di erent position later 9 Insert the oscillator carefully Make sure that the plug is in the correct position 10 Screw in and tighten the two screws with a Phillips sc...

Page 25: ...s carry out the repair quickly and without having to call back for needed information l Print and ll out one form per instrument l Clean the instrument and pack it damage proof l Attach the completed...

Page 26: ...ave purposely de signed the electronic modules to be easily separable WEEE directive 2002 96 EG This instrument is not subject to the WEEE directive 2002 96 EG and the respective national laws in Germ...

Page 27: ...Alu plastic housing Ground terminal 316L Weights with plastic housing 1150 g 40 oz with Aluminium housing 1600 g 56 oz with stainless steel housing 1950 g 69 oz Rod weight 12 mm 0 47 in 900 g m 10 oz...

Page 28: ...32 F 100 C 212 F 150 C 302 F 200 C 392 F Fig 15 Ambient temperature Product temperature 1 Product temperature 2 Ambient temperature 3 Temperature range with temperature adapter Dielectric gure 1 5 Ele...

Page 29: ...iding foil mantle wire cross section 0 5 mm wire resistance 0 036 Ohm m tensile load 1200 N 270 pounds force Standard length 5 m 16 4 ft max length 1000 m 3280 ft Min bending radius 25 mm at 25 C 77 F...

Page 30: ...tion class II Approvals option 3 ATEX II 1G 1 2G 2G EEx ia IIC T6 ATEX II 1 2 D 2 D IP6X T4 Over ll protection acc to WHG applied for Ship approvals applied for 2 Requirement to maintain the protectio...

Page 31: ...Fig 16 Housing versions in protection IP 66 IP 67 and IP 66 IP 68 0 2 bar 1 Plastic housing 2 Stainless steel housing 3 Aluminium housing Housing in protection IP 66 IP 68 1 bar 117mm 4 39 64 103mm 4...

Page 32: ...L G 3 4 A G 1 A G 11 2 A 56 mm 2 1 4 22 2 1 4 Fig 18 VEGACAP 62 Threaded version G1 A L Sensor length see Technical data 73mm 2 7 8 40mm 1 37 64 Fig 19 Temperature adapter Supplement 32 VEGACAP 62 wi...

Page 33: ...Supplement VEGACAP 62 with two wire output 33 30007 EN 060222...

Page 34: ...zrechte N here Informationen unter http www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellectuelle Pour plus d informations on pourra se r f rer au s...

Page 35: ...Supplement VEGACAP 62 with two wire output 35 30007 EN 060222...

Page 36: ...com www vega com ISO 9001 All statements concerning scope of delivery application practical use and operating conditions of the sensors and processing systems correspond to the information avail able...

Reviews: