17
5 Set up with the display and adjustment module
VEGABAR 82 • Slave sensor for electronic differential pressure
46332-EN-160212
Menu item
Parameter
Default setting
Damping
Integration time
0.0 s
Linearization
Linear
Current output
Current output -
Mode
Output characteristics
4 … 20 mA
Reaction when malfunctions occur
≤ 3.6 mA
Current output -
Min./Max.
3.8 mA
20.5 mA
Lock adjustment
Last setting
Menu - Display
Menu item
Default setting
Menu language
Order-specific
Displayed value 1
Current output in %
Displayed value 2
Ceramic measuring cell: Measuring cell tempera
-
ture in °C
Metallic measuring cell: Electronics temperature
in °C
Display format 1 and 2
Number of positions after the decimal point, auto
-
matically
Backlight
Switched on
Reset - Diagnosis
Menu item
Parameter
Default setting
Sensor status
-
Peak value
Pressure
Actual measured value
Temperature
Actual temperature values from meas
-
uring cell, electronics
Simulation
-
Reset - Additional settings
Menu item
Parameter
Default setting
PIN
0000
Date/Time
Actual date/Actual time
Copy in-
strument
settings
-
Special pa-
rameters
-
Scaling
Scaling size
Volume in l
Scaling format
0 % corresponds to 0 l
100 % corresponds to 0 l