57
10 Supplement
VEGABAR 54 • Profibus PA - climate compensated
36790-EN-130321
Status
code
Description according to
Profibus standard
Possible cause
0 x 04
bad - configuration error
–
Adjustment error
–
Configuration error with PV-Scale (PV-Span too small)
–
Unit irregularity
–
Error in the linearization table
0 x 0C
bad - sensor failure
–
Hardware error
–
Converter error
–
Leakage pulse error
–
Trigger error
0 x 10
bad - sensor failure
–
Measured value generation error
–
Temperature measurement error
0 x 1f
bad - out of service constant
"Out of Service" mode switched on
0 x 44
uncertain - last unstable value
Failsafe replacement value (Failsafe-Mode = "Last value" and al-
ready valid measured value since switching on)
0 x 48
uncertain substitute set
–
Switch on simulation
–
Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0 x 4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0 x 51
uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0 x 52
uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0 x 80
good (non-cascade) - OK
OK
0 x 84
good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parame-
ter of the static category has been written)
0 x 89
good (non-cascade) - active ad-
visory alarm - low limited
Lo-Alarm
0 x 8a
good (non-cascade) - active ad-
visory alarm - high limited
Hi-Alarm
0 x 8d
good (non-cascade) - active crit-
ical alarm - low limited
Lo-Lo-Alarm
0 x 8e
good (non-cascade) - active crit-
ical alarm - high limited
Hi-Hi-Alarm
10.3 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded on www.vega.com under "
Downloads
" and "
Drawings
".
The two chamber housings are not available with instruments with 4 … 20 mA signal output