C
ode
T
ext mes
-
sage
C
ause
R
ecti
fi
cation
F
034
EPROM
hard
-
ware error
l
E
lectronics defective
l
E
xchange of the electro
-
nics
F
035
EPROM
data
error
l
E
rror in the internal instru
-
ment communication
l
C
arry out a reset
l
E
xchange of the electro
-
nics
F
036
F
aulty pro
-
gram memory
l
E
rror during software up
-
date
l
R
epeat software update
l
E
xchange of the electro
-
nics
F
037
RAM
hard
-
ware error
l
E
rror in
RAM
l
E
xchange of the electro
-
nics
F
038
S
lave signals
failure
l
C
onnection cable to the
S
lave instrument interrup
-
ted
l
I
nstrument not de
fi
ned as
S
lave instrument
l
D
e
fi
ne instrument as
S
lave
l
C
heck the connection cab
-
le to the
S
lave instrument
F
040
H
ardware er
-
ror
l
S
ensor defective
l
E
xchange of the electro
-
nics
F
041
P
hotomultipli
-
er error
l
E
rror in the measured va
-
lue recording
l
E
xchange of the electro
-
nics
F
045
E
rror on the
current output
l
E
rror on the current output
l
C
heck wiring of the current
output
l
E
xchange of the electro
-
nics
F
052
F
aulty con
fi
-
guration
l
I
nvalid parameter adjust
-
ment
l
C
arry out a reset
F
122
D
ouble add
-
ress on the
multisensor
communicati
-
on bus
l
I
nstrument addresse was
assigned several times
l
C
hange instrument addr
-
esses
F
123
X
-
ray alarm
l
E
xternal instruments
cause radioactive radiation
l
D
etermine reason for
X
-
ray
alarm
l
I
n case of a brief
X
-
ray
alarm
,
shut down the in
-
strument
(
switching
)
out
-
puts for this time
POINTRAC
31
•
F
oundation
F
ieldbus
39
9
D
iagnosis and service