39
8 Maintenance and fault rectification
PLICSMOBILE • Mobile network unit PLICSMOBILE T81
55234-EN-191217
Error
Cause
Rectification
E034
EEPROM CRC error
Switch the instrument off and on
Carry out a reset
Send instrument for repair
E035
ROM CRC error
Switch the instrument off and on
Carry out a reset
Send instrument for repair
E036
Instrument software not
executable (during soft-
ware update and after
failed update)
Wait until software update is finished
Carry out another software update
E042
Hardware error with self-
check
Send instrument for repair
E053
Sensor measuring range
is not read correctly
Communication error: Check sensor
cable and screening
E086
Error communication
hardware (initialisation of
the radio module failed)
Initialisation is carried out automatical-
ly. If the error exists permanently, send
instrument for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Set up
" may have to be carried out again.
8.3 How to proceed if a repair is necessary
You can find an instrument return form as well as detailed informa-
tion about the procedure in the download area of our homepage:
www.vega.com
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
If a repair is necessary, please proceed as follows:
•
Print and fill out one form per instrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please contact the agency serving you to get the address for
the return shipment. You can find the agency on our home page
Note:
If a battery-operated instrument is returned for repair, the battery/
power pack must be removed. Please send only the instrument, not
the battery/power pack.
Reaction after fault recti-
fication