Tank Setup Screens
[131] Tank Setup Screen 4
53
[131] Tank Setup Screen 4
Legend for numbered boxes
1
2
3
4
5
6
01-01-2000
12:00 AM
ALL FUNCTIONS NORMAL
1
TANK 1
[131]
DENSITY CODE
This screen concludes Tank Setup.
1
Density Code [131] - The density float is etched along one side of the device with a unique Density Code which
must be entered in this screen to enable the console to accurately compute the density of the fuel in the tank.
This code is assigned at the factory during calibration of the magnets used in the float. As the density float can
be shipped separately from the probe, the user will need to record the Density Code on each density float and
the tank in which the float is installed. The user will then need to program the console in the above screen with
the selected tank’s float Density Code. The Density Code is exactly 14 characters (e.g., B7053686719512) and
the first letter indicates the float product type - A is for gasoline, B is for diesel.
NOTE: If the Density Code is not available or is not entered into the console during configuration, the
density measured accuracy will default to
±
2 kg/m
3
.