RS-232 Commands
Function Code: 621
44
Function Code: 621
Function Type:
Set Tank Low Level Limit
Version 1
Command Format:
Set:
Inquire:
Display:
<SOH>S621TTVVVVVV
Display:
<SOH>I621TT
Computer:
<SOH>s621TTFFFFFFFF
Computer:
<SOH>i621TT
Notes:
1.
TT -
Tank Number (Decimal, 00 = all)
2.
VVVVVV -
Low Level Limit, (Decimal)
3.
FFFFFFFF -
Low Level Limit, (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I621TT
TT VVVVVV
<ETX>
Typical Response Message, Computer Format:
<SOH>i621TT0000000000TTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. 0000000000 -
Not Used.
2.
TT -
Tank Number (Decimal, 00 = all)
3.
FFFFFFFF -
Low Level Limit, (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC -
Message Checksum