Operations
Alarms
Table 6 summarizes Hose Setup warning messges and Table 7 contains wireless related alarms.
afnn: CHK VAPOR FLOW MTR
Red
Failure of locked rotor test - possible
locked Air Flow Meter.
Locked rotor test passes or Air
Flow Meter deconfigured, or test
cleared.
Table 6. Hose Setup Data Warning Messages
Message
Cause
Action
Label Not Assigned
Missing hose label selection
Check hose settings in Setup>Vapor
Collection>Hose Settings
FP Label Not Set
Fuel Position label not set.
Air Flow Meter Not Assigned
Air Flow Meter not selected and
assigned to the hose.
Assigned Air Flow Meter Not
Configured
Air flow meter is assigned to a
hose but is disabled in Device
Setup.
Check Air Flow Meter setup in
Setup>Device>Air Flow Meter
Meter Not Mapped
Fuel meter not mapped to hose.
Check meter mapping in Setup>Vapor
Collection>Hose Mapping
Table 7. Wireless Related Sensor Alarms
Displayed Message
Devices
Light
Indicator
Description
Suggested
Troubleshooting
BATTERY WARNING
Vapor Valve, VPS,
AFM and Probe
Yellow
Device transmitter reports
battery status as
‘Replace’ for 24 hours
Remove and
replace battery
pack
Table 5: Other Alarms
Displayed Message
Light
Indicator
Set Condition
Clear Condition