9
Setup
Device Setups
ATMOSPHERIC (ATM) PRESSURE SENSOR SETUP - WITH VEEDER-ROOT POLISHER
INSTALLATION ONLY
The ATM Pressure Sensor is factory installed on the USM/ATM Module (P/N 0332818-006). At least one USM/
ATM Module must be installed in the console. You must configure at least one USM/ATM Module for use by the
Vapor Polisher or a PMC Setup Fail will occur. NOTE: if more than one ATM Pressure Sensor is installed, only one
ATM Pressure Sensor needs to be configured.
1. Touch ATM Pressure Sensor in the Devices list (Figure 6) to display the ATM Sensor setup screen (Figure 7).
Figure 6. Accessing ATM Pressure Sensor Setup Screen
2. Touch the Address drop down box to select the address of a USM module ATM sensor. (The ATM on an USM
module is located at address 17.). Touch the Label field to open the keypad and enter a name to identify the