Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
614
RECONCILIATION REPORTS
Function Code:
C01
Version 2
Function Type:
Basic Inventory Reconciliation Daily "Row" Report
Command Format:
Display:
<SOH>IC01PPMMDD
Computer:
<SOH>iC01PPMMDD
Notes:
1.
MMDD - Month and Day for Daily Report
Typical Response Message, Display Format:
<SOH>
IC01PP
MAR 26, 2009 1:43 PM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
MAR 26, 2009 1:43 PM
DAILY RECONCILIATION REPORT
F 1:REGULAR
T 1:REGULAR UNLEADED
T 3:REGULAR UNLEAD EAST
DATE TIME OPENING METERED MANUAL CALC'D PHYSICAL WATER
MAR 25 2:00 AM VOLUME DLVRIES SALES ADJUST INVNTRY INVNTRY HEIGHT VARIANCE
MAR 26 2:00 AM 6081 0 1888 0 4193 4199 0.00 6
SIGNATURE _________________________
<ETX>
Typical Response Message, Computer Format:
<SOH>iC01PPYYMMDDHHmmPPnnTTYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
PPnnTTYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
PP - Product Number (Decimal, 00=All Products)
3.
nn - Number of tanks that are mapped to the product (Decimal)
4.
TT - Tank numbers mapped to product
5.
YYMMDDHHmm - Opening Date and Time
6.
YYMMDDHHmm - Closing Date and Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE floats:
1. Probe measured inventory at previous period close
2. Sum total of adjusted deliveries during period
3. Sum total of all metered sales during period
4. Manually entered adjustments for period
5. Calculated Inventory Volume at period close
6. Probe measured inventory at period close
7. Water Height at period close
8. Variance over period
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum