25
Line Disable Setup
In-Tank Alarms
25-4
3 WIRE C.L. SENSOR ALARMS
If necessary, press STEP until you see the message:
Select 3 Wire C.L. Sensor Alarms (ref. Alarm List in Section 6, Table 6-2).
POWER SIDE DIM ALARMS
If necessary, press STEP until you see the message:
Select Power Side DIM Alarms (ref. Alarm List in Section 6, Table 6-2).
RECONCILIATION ALARMS
If necessary, press STEP until you see the message:
Select Reconciliation Alarms (ref. Alarm List in Section 6, Table 6-2).
PRESSURE LINE LEAK DETECTOR (PLLD) ALARMS
If necessary, press STEP until you see the message:
Select Pressure Line Leak Detector Alarms (ref. Alarm List in Section 6, Table 6-2).
•
OPEN ALARM*
•
HANDLE ALRM*
•
LN EQ FAULT*
*These are the only PLLD alarms that can disable a PLLD line.
WIRELESS PRESSURE LINE LEAK DETECTOR (WPLLD) ALARMS
If necessary, press STEP until you see the message:
Select WPLLD Line Leak Alarms (ref. Alarm List in Section 6, Table 6-2).
•
COMM ALARM*
• HANDLE ALRM*
•
LN EQ FAULT*
*These are the only WPLLD alarms that can disable a WPLLD line.
Q1: (Name)
3 WIRE CL ALARMS: NO
Q1: (Name)
POWER SIDE DIM ALM: NO
Q1: (Name)
RECONCILIATION ALM: NO
Q1: (Name)
PRESSURE LINE LEAK: NO
Q1: (Name)
WPLLD LINE LEAK: NO