Connecting Probe/Sensor Wiring to Consoles
TLS-
3
50/ProMax/EMC Consoles
65
GROUNDWATER SENSOR INTERFACE MODULE - I.S. BAY
Figure 63. Groundwater Sensor Interface Module Wiring
Connecting Device
Connect sensor in the table below to the appropriate terminals on the Groundwater Sensor Interface module as
shown in Figure 63.
Device
Wires
Observe Polarity
4SITE Groundwater Sensor
3
Yes
GROUND
WATER
SENSOR
MAXIMUM SENSOR
OUTPUT RATINGS:
15 VDC
.15 AMP
F G W F G W F G W F G W F G W
1
1
2
2
3
3
4
4
5
5
GROUNDWATER SENSOR INTERFACE MODULE
consoles\gsimw.eps
Console
Not Used
F
W
G
Up to 5
Sensors
Sensor
#1
Sensor
#5
Attach Cable Shields to Ground
Lug Closest to Conduit Entry
F
W
G
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)