 VPS Installation

Before You Begin

4

Before You Begin

• Comply with all recommended safety practices identified by OSHA (Occupational Safety and Health 

Administration) and your employer.

• Review and comply with all the safety warnings in the installation manuals and any other national, State or Local 

requirements.

• When direct wiring to the TLS console, a 2-conductor, 18 AWG shielded cable must be installed in intrinsically 

safe conduit from the dispenser or from the vapor vent stack to the TLS console. The cable length between the 

console and sensor must not exceed the distance stated in the appropriate console’s site prep manual. Conduit 

for direct-wired installations must be properly sealed in accordance with the latest National Electric Code 

(NFPA 70) and the Code for Motor Fuel Dispensing Facilities and Repair Garages (NFPA 30A) since they pass 

from a Class I, Division 1 or 2 hazardous area into a non-hazardous area. 

• Conductors of different intrinsically safe circuits run in the same cable/conduit must have at least 0.01 inch 

(0.25 mm) of insulation.

• For all connections requiring sealant, use only UL classified yellow Gas/TFE plumbing tape.
• Intrinsically safe devices must be installed in accordance with Article 504 of the National Electrical Code, ANSI/

NFPA 70, for installation in the United States, or Section 18 of the Canadian Electrical Code for installations in 

Canada.

• When installing on a vent stack, customer supplied pipe and pipe fittings shall be standard full-weight (ASTM 

Schedule 40) wrought iron or steel.

• Customer supplied copper tubing shall be soft tempered, 1/4-inch O.D., with a minimum wall thickness of 

0.0265 inches.

• Pipe threads shall be in accordance with the Standard for Pipe Threads, General Purpose (Inch) ANSI/ASME 

B1.20.1-1983.

Veeder-Root Parts

Veeder-Root parts and kits required to install the VPS are listed in Table 1 and Table 2.

Table 1. Under Dispenser - VPS Installation Kit (P/N 330020-433 [included in kit 330020-515])

Item

Qty.

Description

P/N

1

1

Vapor Pressure sensor

331946-001 or 861190-201

2

4

Male connector 68CA-4-4, brass 1/4” tube to 1/4” pipe

514100-430

3

1

Union 62CA-4, brass 1/4” tube size

514100-431

4

1

Plug 59CA-4, brass 1/4” tube size

514100-432

5

1

Universal sensor mounting kit - miscellaneous assortment 

of U-bolts, brackets, clamps, and fasteners

330020-012

6

2

Wire nut

576008-461

7

1

Sealing pack

514100-304

8

1

Cord grip

331028-011

9

2

Tie wrap

510901-337

10

1

Shim

332061-001

Summary of Contents for TLS-3 Series

Page 1: ...Manual No 577013 797 Revision P Installation Guide Vapor Pressure Sensor TLS 450PLUS TLS 3XX Consoles...

Page 2: ...signed Bill of Lading BOL to Veeder Root Customer Service at 800 234 5350 3 Veeder Root will file the claim with the carrier and replace the damaged missing product at no charge to the customer Custom...

Page 3: ...stall in Horizontal Access Fitting or Vapor Return Line ISD Installation with Air Flow Meter Below Shear Valve 11 Figure 5 Example VPS Installation Below Vertical Access Fitting or Vapor Return Line I...

Page 4: ...ded safety practices identified by OSHA and your employer Review and comply with all the safety warnings in this an any related documents and any other Federal State or Local requirements Warranty Reg...

Page 5: ...Install Setup Operation Manual TLS 350 For Sites With TLS 450PLUS Consoles 577014 073 TLS 450PLUS Site Prep and Installation Manual 577014 484 Veeder Root ISD For TLS 450PLUS Consoles Install Manual V...

Page 6: ...dress practices not related to physical injury WARNING This product is to be installed and operated in the highly combustible environment of a gasoline dispenser where flammable liquids and explosive...

Page 7: ...ified yellow Gas TFE plumbing tape Intrinsically safe devices must be installed in accordance with Article 504 of the National Electrical Code ANSI NFPA 70 for installation in the United States or Sec...

Page 8: ...S bend 333006 001 10 1 Tube copper 1 4 OD x 8 length 333018 001 11 1 Ball valve 3 way 1 4 576008 649 12 1 Hub conduit liquid tight 1 2 zinc 576010 715 13 3 Conduit clamp 2 steel std duty 514100 478 1...

Page 9: ...m and necessary bolts nuts and washers from the included Universal Sensor Mounting kit Wrap the rubber shim item 10 in Table 1 around the sensor before inserting it into the clamp The VPS sensor must...

Page 10: ...VPS wiring with wire nuts see Figure 6 For Wireless installations skip Steps 11 13 The VPS sensor connects to a TLS RF transmitter not to field wiring from the TLS Console see manual 577013 964 for in...

Page 11: ...enser 2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of...

Page 12: ...2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispe...

Page 13: ...Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispenser cabinet 797 9 eps Pitch to drain 1 4 vertical p...

Page 14: ...sensor before inserting in clamp Pressure sensing port Pitch to drain 1 4 vertical per 12 horizontal 12 4 11 2 2 2 2 3 2 1 10 OR Seal off customer supplied Conduit to TLS Console Cable Cord grip Flow...

Page 15: ...ng port 3 1 10 Seal off customer supplied Conduit to TLS Console Cable Cable Cord grip Flow Meter and Pressure Sensor wiring can share the same conduit to console Observe polarity Required Y fitting f...

Page 16: ...wn in A bend pak along long length 3 As shown in B firmly squeeze the RED SIDE of the resin forcing it through the center seal and into BLACK SIDE 4 Mix thoroughly to a uniform color by squeezing cont...

Page 17: ...4 Figure 8 Direct Wired VPS Connects to Available TLS 450PLUS USM Module Position Figure 9 Direct Wired VPS Connects to Available TLS 3XX Smart Sensor Interface Module Position For wireless configurat...

Page 18: ...e item 2 in Table 2 such that the VPS cable outlet is facing up and the pressure sensing port tube in the base of the sensor is facing down The symbol on the panel should be facing upward Use the four...

Page 19: ...of the tube up and estimate the length needed to loop from the bottom of the drying tube over to the vent port off center of the VPS Cut the Tygon tubing at the estimated length approximately a foot...

Page 20: ...VPS Installation Vapor Vent Stack Installation Wired VPS 1717 Figure 10 Locating Direct Wired VPS Sensor Enclosure on Vapor Vent Stack...

Page 21: ...VPS Installation Vapor Vent Stack Installation Wired VPS 18 Figure 11 Direct Wired VPS Sensor Installed in Vapor Vent Stack Enclosure...

Page 22: ......