Appendix B

Interface To BACnet & Modbus Tables

B-2

Table B-3. Tank Veeder-Root Interface To BACnet And Modbus

Table B-4. Liquid Sensor Veeder-Root Interface Mappings To BACnet And Modbus

Point Name

BACnet Object Type

BACnet Object ID

Modbus Register

Tank X Inventory Volume

AI

X001

30X01

Tank X Inventory TC Volume

AI

X002

30X02

Tank X Inventory Ullage

AI

X003

30X03

Tank X Inventory Height

AI

X004

30X04

Tank X Inventory Water

AI

X005

30X05

Tank X Inventory Temperature

AI

X006

30X06

Tank X Inventory Water Volume

AI

X007

30X07

Tank X Delivery Product Code

AI

X008

30X08

Tank X Delivery Number of Deliveries

AI

X009

30X09

Tank X Delivery Start Time from 01/01/1970

AI

X010

30X10

Tank X Delivery Stop Time from 01/01/1970

AI

X011

30X11

Tank X Delivery Starting Volume

AI

X012

30X12

Tank X Delivery Starting TC Volume

AI

X013

30X13

Tank X Delivery Starting Water

AI

X014

30X14

Tank X Delivery Starting Temp

AI

X015

30X15

Tank X Delivery Ending Volume

AI

X016

30X16

Tank X Delivery Ending TC Volume

AI

X017

30X17

Tank X Delivery Ending Water

AI

X018

30X18

Tank X Delivery Ending Temp

AI

X019

30X19

Tank X Delivery Starting Height

AI

X020

30X20

Tank X Delivery Ending Height

AI

X021

30X21

Tank X Tank Setup Warning

BI

X001

10X01

Tank X Tank Leak Alarm

BI

X002

10X02

Tank X High Water Alarm

BI

X003

10X03

Tank X Overfill Alarm

BI

X004

10X04

Tank X Low Limit Alarm

BI

X005

10X05

Tank X Theft Alarm

BI

X006

10X06

Tank X High Limit Alarm

BI

X007

10X07

Tank X Invalid Height Alarm

BI

X008

10X08

Tank X Probe Out Alarm

BI

X009

10X09

Tank X High Water Alarm

BI

X010

10X10

Tank X Delivery Needed

BI

X011

10X11

Tank X Maximum Level Alarm

BI

X012

10X12

Tank X Gross Leak Test Alarm

BI

X013

10X13

Tank X Monthly Leak Test Alarm

BI

X014

10X14

Tank X Annual Leak Test Alarm

BI

X015

10X15

Tank X Monthly Test Warning

BI

X016

10X16

Tank X Annual Test Warning

BI

X017

10X17

Tank X Monthly Test Alarm

BI

X018

10X18

Tank X Annual Test Alarm

BI

X019

10X19

Tank X Leak Test Active

BI

X020

10X20

Tank X No CSLD Idle Time Warning

BI

X021

10X21

Tank X Siphon Break Active Warning

BI

X022

10X22

Tank X CSLD Rate Increase Warning

BI

X023

10X23

Tank X AccuChart Calibration Warning

BI

X024

10X24

Tank X HRM Reconciliation Warning

BI

X025

10X25

Tank X HRM Reconciliation Alarm

BI

X026

10X26

Tank X Cold Temperature Warning

BI

X027

10X27

Tank X Missing Delivery Ticket Warning

BI

X028

10X28

Tank X Gross Leak Alarm

BI

X029

10X29

Tank X Delivery Density Warning

BI

X030

10X30

Tank X Density warning

BI

X031

10X31

Tank X Fuel Quality Alarm

BI

X032

10X32

Tank X Tank High Temperature Warning

BI

x033

10X33

Tank X Tank Low Temperature Warning

BI

x034

10X34

Tank X Density Offset Warning

BI

x035

10X35

Point Name

BACnet Object Type

BACnet Object ID

Modbus Register

Sensor X Setup Data Warning

BI

X001

10X01

Sensor X Fuel Alarm

BI

X002

10X02

Sensor X Out Alarm

BI

X003

10X03

Sensor X Short Alarm

BI

X004

10X04

Sensor X Water Alarm

BI

X005

10X05

Summary of Contents for QuickServer

Page 1: ...Manual No 577014 367 Revision D Startup Guide QuickServer Industrial Protocol Gateway...

Page 2: ...ur Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Page 3: ...uickServer 9 QuickServer 6 Pin Phoenix Connector 9 Serial Network Wiring Field Port To RS 485 Network 10 Power Up QuickServer 11 Using QuickServer Web Configurator To Setup The Gateway Connect The PC...

Page 4: ...ure A 1 Ethernet Port Location A 1 Figure A 2 Check IP Address A 1 Figure A 3 Error Messages Screen A 2 Figure A 4 Ethernet Port Location A 3 Figure A 5 FS Toolbox Utility Screen A 4 Figure A 6 Select...

Page 5: ...C 1 Table C 2 A Bank DIP Switch Settings For Addresses 51 75 C 2 Table C 3 A Bank DIP Switch Settings For Addresses 76 100 C 3 Table C 4 A Bank DIP Switch Settings For Addresses 101 125 C 4 Table C 5...

Page 6: ...carbon canister vapor polisher installation wireless equipment installation tank and line preparation and line leak detector installation Technician Certification Level 2 3 Contractors holding valid...

Page 7: ...dicates a hazardous situation which if not avoided could result in death or serious injury READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important Read and unde...

Page 8: ...3 Introduction QuickServer Gateway QuickServer Gateway Figure 1 QuickServer ProtoNode Connectivity Diagram TLS450PLUS Shown...

Page 9: ...eeder Root ATG page 9 8 Connect the QuickServer ProtoNode 3 pin RS 485 port to the field protocol cabling page 10 9 Connect power to the QuickServer 6 pin connector page 11 10 Use a web browser to acc...

Page 10: ...Capacity And Registers Per Device The total number of points presented by the device attached to the QuickServer ProtoNode 1504 cannot exceed 5000 The total number of points per QuickServer profile is...

Page 11: ...Desired Protocol Configuration QuickServer ProtoNode units use the S bank of DIP switches S0 S3 to select the protocol configuration see Figure 2 Figure 2 QuickServer S Bank Profile Selections DIP Swi...

Page 12: ...at support Auto Discovery of BACnet MS TP devices Set A bank DIP switches A0 A7 to assign a MAC Address to the QuickServer for BACnet MS TP see Figure 3 Figure 3 QuickServer A Bank DIP Switches Refer...

Page 13: ...quired by the BMS for BACnet MS TP see Figure 4 Figure 4 QuickServer B Bank DIP Switches BMS baud rate dip switch selections are shown in Table 5 Factory default setting Table 5 BMS Baud Rate Baud Rat...

Page 14: ...toNode Connections Device Connections To QuickServer QUICKSERVER 6 PIN PHOENIX CONNECTOR Pins 1 3 are for Veeder Root ATG input see Figure 6 Pins 4 6 are for QuickServer power QuickServer accepts eith...

Page 15: ...connecting to BACnet IP network If the QuickServer is the last device on the trunk then the End Of Line Termination Switch needs to be set to the On position the EOL Termination default setting is Off...

Page 16: ...ty margin should be added to the power supply of the host system A safety margin of 25 is recommended After verifying power source and with frame ground connected as shown in Figure 6 apply power to Q...

Page 17: ...n the 192 168 1 xxx network For Windows 10 Right click on Then click on Network Connections Change Adapter Options Double click on Local Area Connections When the Local Area Connections Status box app...

Page 18: ...Input COM Settings on the device connected to the QuickServer on page 6 for correct COM settings per PLC Type Once a parameter value is changed as desired click Submit to save it The Active profiles s...

Page 19: ...Web Configurator To Setup The Gateway Selecting Profiles for Devices Connected to QuickServer 14 Figure 10 Web Configurator Showing No Active Profiles Figure 11 Web Configurator Showing Available Prof...

Page 20: ...le System and Unknown Type points are automatically configured therefore no profile is required Refer to Table B 1 and Table B 2 in Appendix B for a list of available points Setting BACnet Parameters...

Page 21: ...Using QuickServer Web Configurator To Setup The Gateway Setting BACnet Parameters 16 Figure 13 Web Configurator with Protocol Set to BACnet...

Page 22: ...12 open a web browser on the PC and enter the IP Address of the QuickServer the default address is 192 168 1 24 The Web Configurator is displayed as the landing page see Figure 14 To access the FS GU...

Page 23: ...ess of that managed switch router Click the System Restart button at the bottom of the page to apply changes and restart the QuickServer Unplug Ethernet cable from PC and connect it to the network swi...

Page 24: ...lete all past profiles discovered and or added via Web configurator are deleted The unit can now be reinstalled BACnet EXPLORER NG A typical working example of a BACnet Explorer NG on a BACnet Network...

Page 25: ...at https www sierramonitor com content fieldserver toolbox 0 2 Extract the executable file and complete the installation Figure A 1 Ethernet Port Location 3 Connect a standard CAT5 Ethernet cable betw...

Page 26: ...o connect to the QuickServer 2 Click on Diagnostics and Debugging Button then click on view and then on connections 3 If there are any errors showing on the Connection page refer to Check Wiring And S...

Page 27: ...able A 1 for understanding QuickServer ProtoNode diagnostic LEDs Figure A 4 Ethernet Port Location Table A 1 Diagnostic LED Descriptions LED Description SPL The SPL LED will light if the unit is not g...

Page 28: ...erver Toolbox zip via the Sierra Monitor Resource Center Software Downloads Reference Figure A 1 Extract the executable file and complete the installation Connect a standard CAT5 Ethernet cable betwee...

Page 29: ...For Selected Device d When the capture period is finished the Diagnostic Test Complete window will appear 2 Send Log a Once the diagnostic test is complete a zip file is saved on the PC Figure A 8 Lau...

Page 30: ...Alarm Category If the ProtoNode receives an alarm and or device ID that it does not recognize it will be stored in the DA_UNKCAT data array Only the last device ID Alarm ID and address will be stored...

Page 31: ...Appendix A Securing QuickServer With Passwords A 7 Figure A 9 FS GUI Passwords Page Figure A 10 Password Recovery Page...

Page 32: ...Modbus Register Printer out of Paper BI 1 10001 Printer Error BI 2 10002 EEPROM Configuration Error BI 3 10003 Battery Off BI 4 10004 Too Many Tanks BI 5 10005 System Security Warning BI 6 10006 ROM R...

Page 33: ...arm BI X005 10X05 Tank X Theft Alarm BI X006 10X06 Tank X High Limit Alarm BI X007 10X07 Tank X Invalid Height Alarm BI X008 10X08 Tank X Probe Out Alarm BI X009 10X09 Tank X High Water Alarm BI X010...

Page 34: ...10X05 Point Name BACnet Object Type BACnet Object ID Modbus Register Type B Sensor X Setup Data Warning BI X001 10X01 Type B Sensor X Fuel Alarm BI X002 10X02 Type B Sensor X Out Alarm BI X003 10X03...

Page 35: ...Water Warning BI X006 10X06 Smart Sensor X Water Alarm BI X007 10X07 Smart Sensor X High Liquid Warning BI X008 10X08 Smart Sensor X High Liquid Alarm BI X009 10X09 Smart Sensor X Low Liquid Warning...

Page 36: ...f On Off 33 On Off Off Off Off On Off 34 Off On Off Off Off On Off 35 On On Off Off Off On Off 36 Off Off On Off Off On Off 37 On Off On Off Off On Off 38 Off On On Off Off On Off 39 On On On Off Off...

Page 37: ...Off On Off On On On Off 59 On On Off On On On Off 60 Off Off On On On On Off 61 On Off On On On On Off 62 Off On On On On On Off 63 On On On On On On Off 64 Off Off Off Off Off Off On 65 On Off Off Of...

Page 38: ...On 83 On On Off Off On Off On 84 Off Off On Off On Off On 85 On Off On Off On Off On 86 Off On On Off On Off On 87 On On On Off On Off On 88 Off Off Off On On Off On 89 On Off Off On On Off On 90 Off...

Page 39: ...n On 108 Off Off On On Off On On 109 On Off On On Off On On 110 Off On On On Off On On 111 On On On On Off On On 112 Off Off Off Off On On On 113 On Off Off Off On On On 114 Off On Off Off On On On 11...

Page 40: ...n Off Off Off Off 134 Off On On Off Off Off Off 135 On On On Off Off Off Off 136 Off Off Off On Off Off Off 137 On Off Off On Off Off Off 138 Off On Off On Off Off Off 139 On On Off On Off Off Off 140...

Page 41: ...On On On On Off Off 159 On On On On On Off Off 160 Off Off Off Off Off On Off 161 On Off Off Off Off On Off 162 Off On Off Off Off On Off 163 On On Off Off Off On Off 164 Off Off On Off Off On Off 16...

Page 42: ...On On On Off On On Off 184 Off Off Off On On On Off 185 On Off Off On On On Off 186 Off On Off On On On Off 187 On On Off On On On Off 188 Off Off On On On On Off 189 On Off On On On On Off 190 Off On...

Page 43: ...Off Off Off Off On Off On 209 On Off Off Off On Off On 210 Off On Off Off On Off On 211 On On Off Off On Off On 212 Off Off On Off On Off On 213 On Off On Off On Off On 214 Off On On Off On Off On 21...

Page 44: ...n On Off On Off On On 236 Off Off On On Off On On 237 On Off On On Off On On 238 Off On On On Off On On 239 On On On On Off On On 240 Off Off Off Off On On On 241 On Off Off Off On On On 242 Off On Of...

Page 45: ...on Electrical Connections One 6 pin Phoenix connector with RS 232 port gnd and Power port Frame gnd One 3 pin Phoenix connector with RS 485 port gnd One Ethernet 10 100 BaseT port Approvals CE Certifi...

Page 46: ...ea requiring a key or a special tool to gain access This device must not be connected to a LAN segment with outdoor wiring Certifications BTL Mark BACnet Testing Laboratory BACnet is a registered trad...

Page 47: ...For technical support sales or other assistance please visit www veeder com...

Reviews: