15
TABLE I - High Pressure Thresholds & Warning/Alarm
Software Version
High Pressure Limit
15
40 psi warning
50 psi alarm & shutdown
16 A & B
40 psi warning
50 psi alarm & shutdown
16 C
29 psi warning
30 psi alarm & shutdown
17 & 18
30 psi warning
40 psi alarm & shutdown
19
Not Applicable
TABLE II - Typical Line Pressure
STP Status
Pressure Range
Gauge vs. Console
Off
17 - 25 psi
±5 psi
On
>25 psi
±5 psi
APPENDIX A - TABLES