. Temperature Control Architecture
Section 4.6.
Temp Control Communication
TEMPERATURE CONTROL
The
PID
(Proportional-Integral-Differential) controllers will be responsible for temperature
control of the reactor. Each PID controller will receive two PV signals, TC and
Pyro/RealTemp, via the two PV inputs. The controller will only control using one of the two
PVs, depending on its configuration, but will monitor both PVs continually for
overtemperature
conditions. During shutdown conditions, the
Nexus
system will enable and
disable all power supplies via the power supply (PS) enable output.
OVER-TEMPERATURE CONTROL
The requirements of three hardwired interlocks must be met to enable power supplies.
Those requirements are:
a.
The PLC monitors the system’s upper-level software and disables the power supplies
through processing systems software.