background image

 

TLC3-ECO Economizer 

U

SER 

C

ONFIGURATION

 

 

Doc: 70-00-0660, V1.1, Date: 20170322 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

User and display parameters (password 009) 

 

Parameter  Description 

Range 

Default 

UP 00 

Enable change of operation modes,  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Parameter not used 

ON, OFF 

ON 

UP 03 

Enable manual Heat/Cool change 

ON, OFF 

W00 = ON 

W01 = OFF 

UP 04 

Enable access to time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure: 0 = OFF, 1 = ON, 2 = Last State 

0, 1, 2 

UP 06 

Enable economy (unoccupied) mode.  
Shift the setpoint to a lower temperature in winter or higher 

temperature in summer in order to save energy. May be activated 

through the POWER button. 

ON, OFF 

ON 

(Economy ) 

UP 07 

Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrate internal temperature sensor 
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this 

feature for field adjustment only as required.) 

-10…10 

UP 09 

Calibrate outdoor temperature sensor X1 
–10° to +10° in 0.1° steps.  

-10…10 

UP 10 

Calibrate external temperature sensor X2 
–10° to +10° in 0.1° steps.  

-10…10 

 

UP 11 

Select contents of Large LCD display in standard mode: 

0…6 

 

2  

Indoor 

Temperature 

00 = OFF 

01 = Setpoint 

02 = Control temperature sensor

*1)

 

03 = Output Mode 

04 = Clock 

05 = Outdoor sensor (X1) 
06 = Alternate sensor

*1)

 

 

UP 12 

Select contents of small LCD display in standard mode 

0…6 

Standard:  

5Outdoor 

Temperature 

Deluxe: 

4 Clock 

00 = OFF 
01 = Setpoint 

02 = Control temperature Sensor

*1)

 

03 = Output Mode 

04 = Clock 
05 = Outdoor sensor (X1) 
06 = Alternate sensor

*1)

 

UP 13 

Clock display type: Only available for deluxe version 
OFF = Show 24hour clock 

ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 14 

 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255   = delay in minutes to switch off device if ON/Economy mode 

is activated while the unit is scheduled to be in OFF mode 

0…255 

60 (Min) 

 

*1)

 Control temperature sensor or alternate sensor depends on which sensor is selected as control input with CP18.  

If CP18 = 1:   Control temperature sensor is X2 and alternate sensor is internal temperature sensor 

If CP18

 1:   Control temperature sensor is internal sensor and alternate sensor is X2. 

Summary of Contents for TLC3-ECO Series

Page 1: ...e input heat cool changeover or high low limit The economizer controls an outdoor damper and optional fan It activates the outdoor damper if there is heating or cooling demand and if outdoor condition...

Page 2: ...tic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards conformity RoHS directive...

Page 3: ...diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the mounting screw heads do not stand out more...

Page 4: ...ue Small digits show set point Vertical bars show analog output value Arrows in position 1 2 and or 3 show active binary digital output stages Power failure All parameters and set points are memorized...

Page 5: ...4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set ON or O...

Page 6: ...inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to s...

Page 7: ...ture sensor X1 10 to 10 in 0 1 steps 10 10 0 UP 10 Calibrate external temperature sensor X2 10 to 10 in 0 1 steps 10 10 0 UP 11 Select contents of Large LCD display in standard mode 0 6 2 Indoor Tempe...

Page 8: ...F CP 08 Min temperature difference required to start free cooling 0 10 0 C 1 0 C 2 0 F CP 09 Switching hysteresis is the difference between switching on and switching off A small hysteresis will incre...

Page 9: ...tion Function of mechanical heating or cooling activation If there is heating or cooling demand The controller verifies if free heating or cooling is possible based on control logic mentioned on the l...

Reviews: