Vector OPU-D42-W50 Operation Manual Download Page 2

 

 

Operation terminal OPU-D42-W50 

 

 

Operation terminal OPU-D42-W50 

 

 

Operation terminal OPU-D42-W50 

 

Doc: 70-00-0326B-50, V2.0, 2013-01-07 

© Vector Controls GmbH, Switzerland 

Subject to alteration 

Configuration parameters for firmware version 2.0 –W50 

This controller can be adapted to wide variety of fan coil applications. The adaptation is done with 
parameters. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use 
a matching product version and parameter set. The firmware version is shown on the large LCD digits when 
pressing UP and DOWN buttons for more than 3 seconds simultaneously.  

Changing parameters 

The parameters may only be accessed by entering a code. There are two levels of parameters: User 
operation parameters for access control settings and Expert parameters for control functions and unit setup. 
The codes for user levels and expert levels are different. Only control experts should be given the control 
parameter code.  
The parameters can be changed as follows: 

1. 

Press UP and DOWN button simultaneously for three seconds. The display shows the 
software version in the large digits and the software revision in the small digits.  

2. 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large 
digits. 

3. 

The code for accessing the user parameters is 009 

4. 

Select this using UP or DOWN buttons. 

5. 

Press OPTION button after selecting the correct code.  

6. 

Once logged in, the parameter is displayed immediately. 

7. 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the 
OPTION button. The MIN and MAX symbols show up and indicate that the parameter may 
be modified now. Use UP or DOWN buttons to adjust the value. 

8. 

After you are done, press OPTION or POWER in order to return to the parameter selection 
level.  

9. 

Press the POWER button again so as to leave the menu. The unit will return to normal 
operation if no button is pressed for more than 5 minutes. 

User Parameters (Access Code: 009) 

Parameter  Description 

Range 

Standard 

UP 00 

Enable change of operation modes,  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable manual control fan speeds 

ON, OFF 

ON (Enabled) 

UP 03 

Enable manual change of Heating/Cooling Mode.  
Applies only for 2-pipe or 4-pipe systems.  

ON, OFF 

ON (Enabled) 

UP 04 

Enable Access to time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure: 0 = OFF, 1 = ON, 2 = Last State 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  
Shift the setpoint to a lower temperature in winter or higher 
temperature in summer in order to save energy. May be activated 
through the POWER button, or with the external input (typically 
for key card switches in hotel rooms or motion detectors for 
meeting rooms.)  

ON, OFF 

OFF 

(no economy) 

UP 07 

Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrateinternal temperature sensor 
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this 
feature for field adjustment only as required.) 

-10…10 

UP 09 

Enable Frost Protection. 
Activates the output independent of operation mode when the 
control temperature drops below 5°C or 41°F. The controller 
returns to normal operation when the temperature increases 
above 10°C or 50°F. 

ON, OFF 

ON (Enabled) 

UP 10 

Select contents of Large LCD display in standard mode: 

0…6 

 

02  

Temperature 

00 = OFF 
01 = Setpoint 
02 = Temperature Sensor 

03 = Output Fan Speed 
04 = Clock 
05 = Alternative Sensor 
06 = Output in Percent 

UP 11 

Select contents of small LCD display in standard mode 

0…6 

Standard:  

01 Setpoint 

Deluxe: 

04 Clock 

00 = OFF 
01 = Setpoint 
02 = Temperature Sensor 

03 = Output Fan Speed 
04 = Clock 
05 = Alternative Sensor 
06 = Output in Percent 

UP 12 

Contents of vertical bar in standard mode 
OFF   = Fan Speed 
ON  

= Control output 

ON, OFF 

ON (control) 

UP 13 

Clock display type: Only available for deluxe version 
OFF 

= Show 24hour clock 

ON  

= Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 14 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255   = delay in minutes to switch off device if ON/Economy 

mode is activated while the unit is scheduled to be in 
OFF mode 

0…255 

60 (Min) 

Control Settings (Access Code: 241) 

Warning! Only experts should change these settings!  
Set point limits 

Parameter  Description 

Range 

Standard 

FC 00 

Minimum setpoint limit in Heating mode 

-40-60°C (160°F) 

16°C (61°F) 

FC 01 

Maximum setpoint limit in Heating mode 

-40-60°C (160°F) 

24°C (75°F) 

FC 02 

Minimum setpoint limit in Cooling mode 

-40-60°C (160°F) 

18°C (64°F) 

FC 03 

Maximum setpoint limit in Cooling mode 

-40-60°C (160°F) 

30°C (86°F) 

Fan control sequence 

FC 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) setpoint is shifted by the value 
set with parameter. If heating is active the comfort 
setpoint will be decreased, if cooling is active, the 
setpoint will be increased. (Enable with UP06.) 

0…10.0K (20°F) 

4.0°C (8°F) 

FC 05 

Switching Span Heating,  
if set to 0, only 1 fan speed will be used 

0…10.0K (20°F) 

0.0°C (0.0°F) 

FC 06 

Switching Span Cooling 
if set to 0, only 1 fan speed will be used 

0…10.0K (20°F) 

0.0°C (0.0°F) 

FC 07 

Switching Hysteresis is the difference between 
switching on and switching off. A small hysteresis will 
increase the number of switching cycles and thus the 
wear on fan and relays contacts. 

0…10.0K (20°F) 

0.5°C (1°F) 

FC 08 

Mold Protection:  
In mold protection, the fan keeps running independent 
of temperature as long as the unit is switched on. 

ON, OFF 

ON 

FC 09 

Delay OFF (Minimum running time) 

0…255 s 

10s 

FC 10 

Delay ON (Minimum stopping time) 

0…255 s 

10s 

FC 11 

Control option:  

0 = Cooling only 
1 = Heating only 
2 = 2-pipe system 
3 = 4-pipe system 

0-4 

FC 12 

Dead Zone Span: 
The Dead Zone Span lies between the heating and the 
cooling setpoint. The output is off while the temperature 
is within the dead zone span. A negative dead zone is 
not possible. 

0…100°C (200°F) 

2.0°C (4°F) 

FC 13 

Heat/Cool Changeover Delay (if set to FC11 = 3): 
A demand to switch between heating and cooling must 
persist for the length of time set with this parameter 
before the controller switches. Prevents activation of a 
sequence during a short-term change in temperature in 
order to protect equipment (with control overshoot for 
example) 

0…255 min 

5 min 

PID control sequence 

FC 14 

P – band heating X

PH

 

0…10.0K (20°F) 

2.0°C (4.0°F) 

FC 15 

P – band cooling X

PC

 

0…10.0K (20°F) 

2.0° (4.0°F) 

FC 16 

K

IH

, Integral gain heating, in 0.1 steps, 0 disables ID part 

low value = slow reaction, high value = fast reaction 

0…25.5 

0.0 

FC 17 

K

IC

, Integral gain cooling, in 0.1 steps 

0…25.5 

0.0 

 

Proportional control (P-band)  

The proportional control function calculates the output based on the difference between setpoint and 
measured value. The proportional band (P-band) defines the difference between setpoint and measured 
value which will result in a 100% output. Setting the proportional band to 0 disables proportional control. 

 

 

Integral gain KI 

The integral gain defines how fast the output increases in case the setpoint is not met by the room 
temperature. A low value indicates a slow reaction, a high value a fast one. If the value is chosen too high, 
the controller will start to swing. Depending on the room size and heating / cooling equipment used a value 
between 0.1 and 1.5 should be sufficient. Below are suggested values:  
Heating: KIH: 0.1-0.5, Cooling: KIC: 0.3-0.8

 

Configuration of Analog outputs 

Parameter  Description 

Range 

Standard 

FC 18 

Configuration of analog output signal 
0  =  0-10V 
1  =  2-10V 
2  =  Manual override (useful for commissioning) 

When low fan speed: 25% output 
When medium fan speed 50% output 
When high fan speed 100% output 

0-2 

0 (0-10V) 

FC 19 

Function of analog outputs 
0  =   Disabled 
1  =   Control: Heating only (AO1 only) 
2  =   Control: Cooling only (AO2 only) 
3  =   Control: Heating and cooling (AO1 and AO2) 

0…3 

FC 20 

Output of AO1 in cooling mode if FC19 = 1 or 
Output of AO2 in heating mode if FC19 = 2 

0…100% 

0% 

 

For heating only or cooling only option, the analog output may set to a fixed output while the binary 
sequence is active. This is used for VAV systems. 

 

 

Configuration of binary output 

Parameter  Description 

Range 

Standard 

FC 21 

Function of binary output 
0  =   Disabled 
1  =   Control: Heating only 
2  =   Control: Cooling only 
3  =   Control: Heating and cooling 
4 = 

Enable: On if device is on 

5 =  

Enable: On if device is on and in heating mode 

6 =  

Enable: On if device is on and in cooling mode 

7 =  

Frost protection alarm 

0…7 

FC 22 

Level to activate binary output if in dual AO-DO mode: 
Dual AO-DO mode = both analog and binary outputs 
are assigned to same control sequence.  

0…100% 

65% 

FC 23 

Level do deactivate binary output if in dual AO-DO 
mode 
Dual AO-DO mode = both analog and binary outputs 
are assigned to same control sequence.  

0…100% 

15% 

  The three fan outputs are assigned to the fan speed module. Only output 4 can be assigned by this 

parameter (FC21). Select if the binary output should work as controls output in heating or cooling only 
or both for heating and cooling mode.  

  Dual AO-DO mode: if both the analog and the binary output is assigned as control output to the same 

sequence, the binary output will then switch on when the analog output reaches the value defined in 
FC22 for example 95% and switch off when it drops below FC 23  for example 45%. Note: This output 
does not follow min running and stopping delays. It only reacts to the conditions mentioned above. In 
order to take advantage of this function we recommend using larger proportional bands.  

Configuration of inputs 

FC 24 

External input:  
0 = No external input 
1 = External temperature sensor 
2 = Occupation sensor – Comfort / Economy 
3 = Occupation sensor – Comfort / Off 
4 = Heat / Cool changeover 
5 = Key card with alternative setpoint 
6 = Key card with full reset 

0…6 

FC 25 

Activation delay (Minutes) = the time the binary input 
needs to be open before economy/off mode is activated. 

0…255 min 

FC 26 

Auto-changeover limit heating FC24 = 4 
or economy setpoint in heating mode if FC24 = 5 

-40…60°C (160°F) 

28°C (82°F) 

FC 27 

Auto-changeover limit cooling FC24 = 4 
or economy setpoint in cooling mode if FC24 = 5 

-40…60°C (160°F) 

18°C (64°F) 

FC 28 

Comfort setpoint in heating mode if FC24 = 6 

-40…60°C (160°F) 

21°C (70°F) 

FC 29 

Comfort setpoint in cooling mode if FC24 = 6 

-40…60°C (160°F) 

24°C (75°F) 

Configuring the function of the external input 

FC24 = 1 

External control 
input 

The external sensor is the control input.  

FC24 = 2 

Switching 
Economy and 
Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are controlled 
through an external contact by connecting the input through a dry contact 
to signal common. This function may be used together with key card 
switches for hotels or motion detectors for offices.

 

FC24 = 3 

Switching Energy 
Hold OFF and 
Comfort modes 

Opening the input will force the unit into the OFF operation mode. The 
operation mode cannot be overridden by using the terminal. Connecting 
the input to signal common returns control of the operation mode to the 
terminal. This function may be used as window contact to prevent loss of 
energy.  

FC24 = 4 

Heat – Cool 
changeover 

Switch heating and cooling mode based on supply media or outside 
temperature or binary contact. See below for further details.  

FC24 = 5 

Key card with 
alternative 
setpoint 

As with FC24 = 2, the key card function switches economy (unoccupied) 
and comfort (occupied) modes. Instead of using the setpoint shift, the 
setpoints in unoccupied mode are defined by parameter FC26 in heating 
mode and FC27 in cooling mode. 
Fan speed in unoccupied mode is limited to low speed.  
Fan speed and setpoint will be remembered after re-inserting the key card.  

FC24 = 6 

Key card with full 
reset 

Similar as FC24 = 5 with the difference that setpoints, fan speed and 
operation mode are reset each time the key card is inserted. This is helpful 
for business hotels. Setpoints will be reset to FC28 or FC29.  

 

Configuring auto changeover input if FC24 = 4:  

The auto changeover function automatically changes heating and cooling mode based on supply 
media temperature or outdoor temperature. The difference between the two is in the values of the 
changeover limits FC26 and FC27. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all 
signal ground levels of involved controllers must be the same in case more than one controller is 
switched.  

Recommended settings for FC26 and FC27: 

Change over mode FC24=4 

Relation FC26 to FC27 

Example:FC26 

Example:FC27 

Supply media 

FC26> FC27 

28°C (82F) 

18°C (64F) 

Outside temperature 

FC26< FC27 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

FC26> FC27 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

FC26< FC27 

15°C (59F) 

25°C (77F) 

 