Vector OPA-D5 Operation Manual Download Page 2

 

 

Operation terminal OPA-D5F, OPU-D5F 

 

 

Operation terminal OPA-D5F, OPU-D5F 

 

 

Operation terminal OPA-D5F, OPU-D5F 

 

Doc: 70-00-0789, V2.1, 20130702 

© Vector Controls GmbH, Switzerland 

Subject to alteration 

User parameters (access code: 009) 

Parameter  Description 

Range 

Standard 

UP 00 

Enable change of operation modes,  

ON, OFF 

ON (enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (enabled) 

UP 02 

Enable manual control fan speeds 

ON, OFF 

ON (enabled) 

UP 03 

Enable manual change of heating/cooling/fan only mode  
0 = manual mode change disabled 
1 = fan only enabled 
2 = manual heat/cool mode change enabled 
3 = manual heat/cool/fan only mode enabled 

0, 1, 2, 3 

W00: 3  

(heat/cool/fan 

only) 

W01: 1  

(fan only) 

UP 04 

Enable access to time programs 

ON, OFF 

ON (enabled) 

UP 05 

State after power failure: 0 = OFF, 1 = ON, 2 = Last State 

0, 1, 2 

UP 06 

Enable economy (unoccupied) mode.  
Shift the set point to a lower temperature in winter or higher 
temperature in summer in order to save energy. May be 
activated through the POWER button, or with the external input 
(typically for key card switches in hotel rooms or motion 
detectors for meeting rooms.)  

ON, OFF 

ON 

(economy ) 

UP 07 

Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrate internal temperature sensor  
–10 ° to +10 ° in 0.1 ° steps. (Sensor is factory calibrated; use 
this feature for field adjustment only as required.) 

-

10…10 

UP 09 

Enable frost protection.  
Activates the output independent of operation mode when the 
control temperature drops below 5 °C or 41 °F. The controller 
returns to normal operation when the temperature increases 
above 10 °C or 50 °F. 

ON, OFF 

W00 = ON 

W01 = OFF 

UP 10 

Select contents of Large LCD display in standard mode: 

0…6 

 

02  

Temperature 

00 = OFF 
01 = Set point *1) 
02 = Temperature sensor 

03 = Output fan speed 
04 = Clock 
05 = Alternative sensor 
06 = Output in percent 

*1) Note: if UP10 = 1, the set point will be shown instead of the 
measured temperature also in controls display.  

UP 11 

Select contents of small LCD display in standard mode  

0…6 

Standard:  

01 Set point 

Deluxe: 

04 Clock 

00 = OFF 
01 = Set point 
02 = Temperature sensor 

03 = Output fan speed 
04 = Clock 
05 = Alternative sensor 
06 = Output in percent 

UP 12 

Contents of vertical bar in standard mode 
OFF   = Fan speed 
ON  

= Control output 

ON, OFF 

OFF (fan) 

UP 13 

Clock display type: Only available for deluxe version 
OFF 

= Show 24 hour clock 

ON  

= Show 12 hour clock (AM, PM) 

ON, OFF 

OFF (24 h) 

UP 14 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255   = delay in minutes to switch off device if on/economy 

mode is activated while the unit is scheduled to be 
in off mode 

0…255 

60 (min) 

Control parameters (access code: 241) 

Warning! Only experts should change these settings!  
Set point limit parameters 

Parameter 

Description 

Range 

Standard 

FC 00 

Minimum set point limit in heating mode 

-40

…60 °C 

(160 °F) 

16 °C (61 °F) 

FC 01 

Maximum set point limit in heating mode 

-40

…60 °C 

(160 °F) 

24 °C (76 °F) 

FC 02 

Minimum set point limit in cooling mode 

-40

…60 °C 

(160 °F) 

18 °C (65 °F) 

FC 03 

Maximum set point limit in cooling mode 

-40

…60 °C 

(160 °F) 

30 °C (87 °F) 

Control Loop Parameters 

FC 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) set point is shifted by the value set with 
parameter. If heating is active the comfort set point will be 
decreased, if cooling is active, the set point will be increased. 
(enable with UP06.) 

0

…10.0 °C 

(20 °F) 

5.0 °C (10 °F) 

FC 05 

Switching span heating 

0

…10.0 °C 

(20 °F) 

0.9 °C (1.8 °F) 

FC 06 

Switching span cooling 

0

…10.0 °C 

(20 °F) 

0.7 °C (1.4 °F) 

FC 07 

Switching hysteresis is the difference between switching on and 
switching off. A small hysteresis will increase the number of 
switching cycles and thus the wear on fan and relays contacts. 

0

…10.0 °C 

(20 °F) 

0.5 °C (1 °F) 

FC 08 

Mold protection: OFF = disabled, ON = enabled 

ON, OFF 

OFF 

FC 09 

Delay OFF (minimum running time) 

0…255 s 

10 s 

FC 10 

Delay ON (minimum stopping time) 

0…255 s 

10 s 

PID  Parameters 

FC 11 

P- band heating X

PH

 

0…10.0K (20 °F)  2.0 °C (4.0 °F) 

FC 12 

P- band cooling X

PC

 

0…10.0K (20 °F)  2.0 ° (4.0 °F) 

FC 13 

K

IH

, Integral gain heating, in 0.1 steps,  

0 disables ID part 
low value = slow reaction 
high value = fast reaction 

0…25.5 

0.0 

FC 14 

K

IC

, Integral gain cooling, in 0.1 steps 

0…25.5 

0.0 

 

Proportional control

 

(P-band)  

The proportional control function calculates the output based on the difference between set point and 
measured value. The proportional band (P-band) defines the difference between set point and measured 
value which will result in a 100% output. Setting the proportional band to 0 disables proportional control. 

 

 

Output Parameters 

FC 15 

FO1: Enable floating output (DO4 OPEN, DO5 CLOSE)  

ON, OFF 

ON 

FC 16 

FO1: Running time of actuator 

0

…255 s 

90 s 

 

 

3-point floating:  

For floating point outputs the running time of the actuator used needs to be specified with FC16. Running 
time is defined as the time required for the actuator to run from fully open to fully closed and vice versa. 
Actuators with a fixed running time are recommended. Once fully open or fully closed the running time for 
the actuator is extended for a full run-time cycle. This will allow the actuator position to be synchronized in 
case it has been moved during off time or an actuator with variable running time was used.

 

Input parameters 

Parameter  Description 

Range 

Standard 

FC 17 

External input:  
0 = No external input 
1 = External temperature sensor 
2 = Occupation sensor 

– comfort / economy 

3 = Occupation sensor 

– comfort / off 

4 = Heat / cool change by open contact. Contact open = heat 
5 = Heat / cool change by open contact. Contact open = cool 
6 = Auto-changeover based on supply temperature 
7 = Auto-changeover based on outside temperature 
8 = Key card with alternative set point 

0…8 

FC 18 

Activation delay (minutes) = the time the binary input needs to be 
open before economy/off mode is activated. 

0…255 min 

FC 19 

Auto-changeover limit cooling for supply temperature FC17 = 6 
Auto-changeover limit heating for outside temperature FC17 = 7 
or economy set point in heating mode if FC17 = 8 

-

40…60 °C 

(160 °F) 

16 °C 

(61 °F) 

FC 20 

Auto-changeover limit heating for supply temperature FC17 = 6 
Auto-changeover limit cooling for outside temperature FC17 = 7 
or economy set point in cooling mode if FC17 = 8 

-

40…60 °C 

(160 °F) 

28 °C 

(83 °F) 

 

 

Configuring the function of the external input 

 

FC17 = 0 

Input not used 

 

FC17 = 1 

External control input 

The external sensor is the control input. The internal 
sensor will be disabled.  

FC17 = 2 

Switching economy and 
comfort modes 

Economy (unoccupied) and comfort (occupied) modes 
are controlled through an external contact by 
connecting the input through a dry contact to signal 
common. This function may be used together with key 
card switches for hotels or motion detectors for offices.

 

FC17 = 3 

Switching energy hold 
off and comfort modes 

Opening the input will force the unit into the OFF 
operation mode. The operation mode cannot be 
overridden by using the terminal. Connecting the input 
to signal common returns control of the operation mode 
to the terminal. This function may be used as window 
contact to prevent loss of energy.  

FC17 = 4 

Heat 

– cool change-

over by contact 

Switch by open contact: Contact open = heating is 
active, contact closed = cooling is active.  

FC17 = 5 

Heat 

– cool change-

over by contact 

Switch by open contact: Contact open = cooling is 
active, contact closed = heating is active.  

FC17 = 6 

Auto heat cool change-
over by supply 
temperature 

Connect a supply media sensor to the input. Cooling 
will be activated if a temperature below FC19 is 
measured. Heating is activated if a value above FC20 is 
measured 

FC17 = 7 

Auto heat cool change-
over by outdoor 
temperature 

Connect an outdoor temperature sensor to the input. 
Cooling will be activated if a temperature above FC20 is 
measured. Heating is activated if a value below FC19 is 
measured 

FC17 = 8 

Key card with 
alternative set point 

As with FC17 = 2, the key card function switches 
economy (unoccupied) and comfort (occupied) modes. 
Instead of using the set point shift, the set points in 
unoccupied mode are defined by parameter FC19 in 
heating mode and FC20 in cooling mode. 
Fan speed in unoccupied mode is limited to low speed.  

 

Reviews: