Modbus access (TRA-F221-A only)
The controller supports the following Modbus function cods:
Modbus function code
Data
Read multiple register (0x03)
Read n registers (n x 2 bytes) starting from requested address.
Write register (0x06)
Write 1 register (2 bytes) at requested address.
Write multiple registers (0x16)
Write n register (n x 2 bytes) starting from sent address.
Note: The read/write capability of each parameter is defined in column “R/W”. Most parameters can
be read and written
defined as “R/W”. Read only parameters are defined as “R”.
5.2
Setting controller parameter with user interface
Entering the password protected parameter menu
1.
Press the up ( ) and down ( ) button for at least 3 seconds.
2.
The software version is displayed.
3.
To continue to the password menu, press ether the up ( ), down ( ) or fan button ( ).
4.
Enter the code
241
with the up ( ) or down ( ) button.
5.
Confirm the code with the fan button ( ).
Software version (example) Password
Password entered
Password not valid
Setting parameters
1.
Press the up ( ) or down ( ) button to select the desired parameter.
2.
To set the value of parameter, press the fan button ( ) then adjust the value with the up ( ) or down ( )
button and save the setting by pressing the fan button ( ) again.
Exit the parameter menu
Press the Operating ( ) or Controlling ( ) Mode button to leave the parameter menu.
5.3
Modbus settings (TRA-F221-A only)
5.3.1
Parameter P00x overview
Each Modbus slave device needs a unique device address (ID) in the network. It can be set with P001. All other Modbus
network properties can be set with parameter P002, P003 and P006.
With parameter P005 the write access to the parameter via Modbus master is disabled (except P005 can always be
written).
P004 is not used.
Par/
Addr
Description
Data type / value
Default
R/
W
P001 Modbus device address (ID)
Address range: 1…247
1
R/
W
P002 Baud Rate Modbus RS485
0 = 2400 BPS
1 = 4800 BPS
2 = 9600 BPS
3 = 19200 BPS
4 = 38400 BPS
5 = 57600 BPS
6 = 115200 BPS
4
R/
W
P003 Parity and stop bits
0 = NO Parity, 2 stop bits
1 = EVEN Parity, 1 stop bit
2 = ODD Parity, 1 stop bit
3 = NO Parity, 1 stop bit
1
R/
W
P004 Mode of communication
Not used (always 1 = RTU)
1
R
P005
Allow changing of parameter settings through
communication
0 = Not allowed (except P005)
1 = Allowed
1
R/
W
P006 Modbus address PLC style
0 = No offset
1 = PLC address style (+1 address offset)
0
R/
W