![Vectaire WHHR400DC Installation, Operating And Maintenance Instructions Download Page 6](http://html1.mh-extra.com/html/vectaire/whhr400dc/whhr400dc_installation-operating-and-maintenance-instructions_858721006.webp)
WHHRM300DC & WHHR400DC 3
2.3 Technical information
WHHRM300DC WHHR400DC
Supply voltage [V~/Hz]
230/50
Protection degree
IP31
Dimensions (w x h x d) [mm]
675 x 602 x 420
675 x 602 x 430
Duct diameter [mm]
Ø150
Ø180
External diameter condensate discharge [mm]
Ø20
Weight [kg] (Excl. bypass unit of 3.5 kg)
31
32
Filter class
G3 (F6 optional)
Fan setting
1
2
3
1
2
3
Ventilation capacity [m
3
KUHVSHFWLYHO\@)DFWRU\
settings
100
150
225
100
200
300
Permissible resistance in the ducting [Pa]
Rated power [W]
Rated current [A]
0.2
&RVij
0.54
Noise capacity
level Lw (A)
Static pressure [Pa]
40
80
160
40
80
240
Housing emission [dB(A)]
28.5
38
46.5
<32
42
52.5
Duct “from dwelling” [dB(A)]
<24
33
41
<30.5
38
46.5
Duct “to dwelling”
48.5
56
66
51.5
61.5
69
Version
Chapter 2
Bypass unit
Supply voltage [V/Hz]
230/50
Protection degree
IP31
Dimensions (w x h x d) [mm]
675 x 602 x 85
Weight [ kg]
3.5
Rated power [W]
5
Rated current [A]
0.02