Operating manual
Document nr. : 010346
Version :
V1.4
MC 785-DF KLIMA ALFANET
Client : General
Page :
11 of 20
Nr
Description
Range
Unit
Default
P 110
P 111
P 112
P 113
Switch off delay fan
Switch on temperature fan after defrost
Switch on delay fan after defrost
Drainage time
0..99
-40..+50
0..99
0..99
minutes
E
C
minutes
minutes
0
2.0
0
0
P 120
P 121
P 122
P 123
P 124
P 125
P 126
P 127
P 128
Defrost mode
0 =
no defrost
1 =
natural defrost
2 =
elektric defrost
3 =
hot gas defrost
Defrost interval
Maximum defrost time
End of defrost temperature
Defrost release temperature
If the evaporator temperature is higher
than the release temperature the
defrost is not started.
Defrost relay during natural defrost active
Defrost based on compressor run time
Display fixed during defrost
Maximum time display fixed
0..3
1..99
1..99
-10..+30
-40..+50
0 = no, 1 = yes
0 = no, 1 = yes
0 = no, 1 = yes
1..99
-
hours
minutes
E
C
E
C
-
-
-
minutes
0
12
30
5.0
2.0
0
0
0
15
P 130
P 131
P 132
P 133
P 134
P 135
P 136
P 137
If cooling on then
0 =
nothing off
1 =
humidify off
2 =
dehumidify off
If heating on then
0 =
nothing off
1 =
humidify off
2 =
dehumidify off
If humidify on then
0 =
nothing off
1 =
cooling off
2 =
heating off
If dehumidifying is active then
0 =
notthing
1 =
cooling off
2 =
heating off
Dehumidifying by
0 =
nothing
1 =
cooling contact
2 =
heating contact
During humidifying fan on
During dehumidifying fan on
During heating fan on
0..2
0..2
0..2
0..2
0..2
0 = no, 1 = yes
0 = no, 1 = yes
0 = no, 1 = yes
-
-
-
-
-
-
-
-
0
0
0
0
0
0
0
1
P 140
Day/night function
0 =
day/night function off
1 =
day/night function on
2 =
day/night function on and
humidity control off
0..2
-
0