VDH LNG EXT RS D/N User Manual Download Page 3

User manual

 Document no. : 110882

 Version:  

V1.0

LNG EXT RS D/N Control panel general

 Client:  Heinen & Hopman

 Page:      

3 of 6 

TECHNICAL DATA

:

Type

: Controller panel LNG EXT RS D/N 3M/4-Keys

 (SET, DOWN, UP,D/N)

Type numbers

: 944.801679  Vimar Eikon, front black

 (without coverplate)

Method of mounting

: Panel mounting on f.i. bticino/Playbus/Vimar/.. 3M(3-Modules) systems

Connections

: At rear side

Cable fitting

: screws

Dimension housing

: Depends on Cover/Frame with maximum depth 50mm

Power supply

: 24Vac G/Go

(Go is internal connected to Gnd)

Power supply tol.

: +/-10%

Input temperature sensor

: KTY81 2-wire bn/wh 

(external)

Measuring system

: 2-wire

Measuring range

: 0/+30°C

Accuracy

: 0.5°C

Readout

: Digital 3-digit

Output signals

: Measuring signal B1/M1

9°C = 2,6V (-50mV/°C), 

Comp. setpoint signal Z1/M8

9°C/29°C = +1,0/+9,0V

Communication

: RS485 network A/B/Gnd  

(2xTwisted-pair shielded min.0,5mm

2

)

Storage temp.

: -20/+40°C

Working temp.

: -5/+35°C

FACTORY SETTINGS:

Adjusting potentiometers;

There  is  an  adjusting  screw  (set-screw)  on  the  side  with  which  the  measured  value  can  be
adjusted. The output power appropriate to the measuring value can be measured between the
screws B1 and M (19°C = 2,60V (-50mV/°C)  f.i. 20°C = 2,55V).

CONTROL

:

Adjusting the setpoint

:

Hold down the 

SET

 key and set the desired value using the 

UP

 or 

DOWN

 keys 

(adjustment per 0.1°C).

Switching display on / off

:

By pressing the 

UP

 key and the 

DOWN

 key simultaneously the display can be turned off. 

Press any key and the display will come on again.

Switching day/night mode

:

By pressing the 

DAY/NIGHT

 key the controller can be switched to day or night mode. 

The current day/night mode of the controller is shown on the front of the controller by two LED’s
(DAY and NIGHT) next to the display.  
The controller starts at power-up always in day mode.