VDH ALFANET 79 User Manual Download Page 2

2

* Sensor adjustment.

The humidity-sensor can be adjusted by using the Offset Humidity sensor (parameter 05).
Indicates the 

ALFANET 79

 e.g. 2% too much, than the Offset Humidity sensor (parameter 05) has

to be decreased with 2%.

* Error messages.

In the display of the 

ALFANET 79

 the following error messages can appear:

rLO

- Minimum RH alarm.

Solution E1:

rHI

- Maximum RH alarm.

- Check if sensor is connected correctly.

E1

- RH sensor failure.*

- Check RH-signal. (0/+100%RH=0/+1Vdc)
- Replace sensor.

EE

- Settings are lost.

Solution EE:
- Reprogram the settings.

*)

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

  and 

-L-

, as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 

 and 

-H-

, as indication for  a open circuit sensor.

* Reset Alarm.

When a error-messages appears it can be reset by pushing the 

SET

 key. The function of this key

depends on parameter P37.

* Technical details.

Type

: ALFANET 79 Hygrostat.

Range

: 0/+100%RH read-out per 1%RH

Read out

: 3-digit 7-segments display

Status LEDs

: LED 'SET' and  LED 'RH'

Supply

: 12 Vac 50/60Hz (-5/+10%).

Relays

: Ry1= SPST(NO) 250V/8A (cos 

φ=1) of 250V/5A (cos φ=0.4)

  Ry2= SPST(NO) 250V/8A (cos 

φ=1) of 250V/5A (cos φ=0.4)

  Ry3= SPDT(NO/NC) 250V/8A (cos 

φ=1) of 250V/5A (cos φ=0.4)

  The three relays have one common (C).

Control

: Thru pushbuttons on front.

Front

: Polycarbonate.

Sensor

: RH 95-2 (+12Vdc; 0/+100%RH = 0/+1Vdc)

Communication

: RS485-Network (2-wire shielded min. 0,75mm

2

; A, B and GND)

Dimensions

: 35 x 77 x 71,5mm (HWD). 

Panel-cutout

: 29 x 71mm (HW).

Accuracy

: ± 0,5% of range.

- Provided with memory protection during power failure.
- Equipped with self-test function and sensor-failure detection.
- Connection with screw-terminals.
- Special version on request available.