VDH ALFANET 79 User Manual Download Page 1

1

User manual
ALFANET 79
Hygrostat.

VDH doc: 010668

Version: v1.0

Datum:19-03-2001

Software: ALFA(NET)79

File: Do010668.WP8

Range: 0/+100%RH

* Installation.

On the topside of the 

ALFANET 79

 is shown how the sensor, power supply and relays has to be

connected.
After connecting the 

ALFANET 79

 to the power supply, a self test function is started. As this test is

finished the measured humidity appears in the display. 
And adjustable thru the 

ALFANET PC-INTERFACE

 on the PC. 

* Control.

The 

ALFANET 79

 Hygrostat can be controlled by four push buttons on the front. These keys are:

SET

- view / change setpoint and reset alarm.

UP

- increase value.

DOWN

- decrease value.

%RH

- hidden key above 

SET

 key and behind %RH symbol.

* View setpoint.

By pushing the 

SET

 key the setpoint appears in the display. The decimal point of the last display

starts blinking to indicate this. After a few seconds after releasing the 

SET

 key the setpoint

disappears  and the measured temperature is shown again.

* Changing setpoint.

Push the 

SET

 key and the setpoint appears in the display. Release the 

SET

 key. Now push the

SET

 key again together with the 

UP

 or 

DOWN

 keys to change the setpoint. After a few seconds

after releasing the 

SET

 key the setpoint disappears  and the measured temperature is shown

again.

* Status of the Relays.

By pushing the hidden 

°C

 key the display shows the status of the relays. Each display segment

shows the status of the relay output, showing 0= off and 1=on. The code 110 means relay 1 and
relay 2 are on and relay 3 is off.

* Setting internal parameters.

Next to the adjustment of the setpoint, some internal settings are possible like differentials,
sensor-adjustments, setpoint-range and function of  the hygrostat.
By pushing the 

DOWN

 key for more than 10 seconds, you enter the  'internal program-ming

menu'. 
In the left display the upper and the lower segments are blinking. Over the 

UP

 and 

DOWN

 keys

the required parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing

the 

UP

 and 

DOWN

 keys allows you to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFANET 79

 changes to it’s normal operation mode.