VDH ALFANET 20 User Manual Download Page 3

3

* Adjustment sensor.

The sensor can be adjusted by using the Sensor Offset (parameter 04). 
Indicates  the 

ALFA(NET)  20

  e.g.  2

C  too  much,  the  Sensor  Offset  has  to  de

decreased with 2

C.

* Error messages.

In the display of the 

ALFA(NET) 20

 the following error messages can appear:

Er

- Sensor broken.  Solution:

- Check if the sensor is connected correctly.
- Check the sensor (1000

 at 25

C).

- Replace the sensor.

EE

- Settings are lost.  Solution:

- Reprogram the settings.

* Technical details.

Model

: ALFA 20 Thermometer
  ALFANET 20 Thermometer with Network

Range

: -50/+50

C, readout per 1

C (or else see Sticker)

Supply

: 230Vac / 2,5VA 50/60Hz (or else see Sticker)

Control

: by hidden push buttons on the front.

Communication

: RS485-Network   (2x twisted pair shielded, min. 0,5mm

2

)

Front

: Polycarbonate

Sensor

: SM 811/2m (1000

 at 25

C)

Dimensions

: 144 x 72 x 50mm (hbd)

Panel hole

: 139 x 67mm (hb) cutout in front

- Provided with memory protection during power failure.
- Connection with screw terminals on the back side.
- Equipped with self test function and sensor failure detection.
- Special version on request available.