VDH ALFA 75 RTDF Manual Download Page 4

 

ALFA(NET) 75 RTDF -50/+50°C 

Doc.no.: 150014   version 1.0 

 

 

 

 

    

 

Page 4 of 8 

12

 

Adjustment sensors 

The temperature sensor (control) can be adjusted by using the Sensor Offset parameter 05. 

The defrost sensor can be adjusted by using the Sensor Offset parameter 07. 

Indicates a Sensor e.g. 2°C too much, then the according Sensor Offset has to be decreased with 
2°C. 

13

 

Technical data 

Type 

ALFA 75 RTDF or 

ALFANET 75 RTDF  

Range 

-50,0/+50.0°C   

 

Readout per 0,1°C 

Supply 

12 Vac / 16,5 Vdc    

 

(-5/+10%) 

Or else see sticker 

Display 

3-digit 7-segment  

 

LED display 

Status LED’s 

COMPR., FAN and DEFR.    

On display thru hidden °C key 

Sensor 

SM 811  2-Wire  

 

PTC 1000

Ω

/25°C 

Relays 

Ry1 Cool= SPST (NO)  

 

250V/8A cos

n

=1 or 250V/5A cos

n

=0.4 

Ry2 Fan = SPST (NO)  

 

250V/8A cos

n

=1 or 250V/5A cos

n

=0.4 

Ry3 Defrost = SPDT (NO/NC)  250V/8A cos

n

=1 or 250V/5A cos

n

=0.4 

Relays have one common (C) 

Communication 

RS-485 Network  

 

Twisted-pair shielded, min. 0,5mm

2

 

only at ALFANET 

 

A, B, 0V  (Twist A and B) 

Control 

By four push buttons  

 

On the front 

Front 

Polycarbonate 

Dimensions 

35 x 77 x 71,5 mm  

 

(H x W x D) 

Panel cut out 

29 x 70 mm  

 

(H x W) 

Accuracy 

+/- 0,5% of the range 

 
 

- Provided with memory protection during power failure. 

 

- Connection with screw terminals. 

 

- Equipped with senor failure detection. 

 

- Special versions are on request available. 

14

 

Setting internal parameters 

Next  to  the  adjustment  of  the  setpoint,  internal  settings  can  be  made  like  differential,  sensor 

adjustments, setpoint-range, compressor-, fan-, defrost- and alarm-settings. 

Push the DOWN key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the 
left  display  the  upper-  and  lower-segment  are  blinking 

.  With  the  UP  and  DOWN  keys  the 

required parameter can be selected (see the parameter table). 

If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing 
the UP or DOWN key together with the SET key to change the value of this parameter. 

If  after  20  seconds  no  key  is  pushed,  the  ALFA(NET)  75  RTDF  changes  to  the  normal  operation 
mode. 

Summary of Contents for ALFA 75 RTDF

Page 1: ...e to be connected After connecting the ALFA NET 75 RTDF to the power supply a self test function is started As this test is finished the measured room temperature of the temperature sensor control app...

Page 2: ...the DOWN keys simultaneously 8 Fan control The ALFANET 75 RTDF has several parameters for fan control Normally the fan is always active Accept for one of the following parameters to be set to 1 the f...

Page 3: ...TDF works normally Parameter 33 1 Compressor active at defrost if P24 1 For hot gas defrost systems the compressor needs to be activated while defrosting After defrost the drip off time P27 starts Dur...

Page 4: ...0 5mm2 only at ALFANET A B 0V Twist A and B Control By four push buttons On the front Front Polycarbonate Dimensions 35 x 77 x 71 5 mm H x W x D Panel cut out 29 x 70 mm H x W Accuracy 0 5 of the rang...

Page 5: ...0 23 Switch off delay fan 0 99 Minutes 0 24 Defrost mode 0 only fan relay 1 only defrost relay 0 Natural 1 Hotgas Elec 0 25 Switch on delay temperature fan after defrost 50 0 50 0 C 2 0 26 Switch on...

Page 6: ...ours Off 66 Defrost time 3 Minutes steps 10 Min 0 50 Off Min Off 67 Defrost time 4 Hours 0 23 Off Hours Off 68 Defrost time 4 Minutes steps 10 Min 0 50 Off Min Off 69 Defrost time 5 Hours 0 23 Off Hou...

Page 7: ...ALFA NET 75 RTDF 50 50 C Doc no 150014 version 1 0 Page 7 of 8 15 Connections Transformer needed at 230Vac power supply...

Page 8: ...Doc no 150014 version 1 0 Page 8 of 8 16 Dimensions 17 Address VDH Products B V Tel 31 0 50 30 28 900 Productieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Inte...

Reviews: