VDH ALFA 51 User Manual Download Page 2

* Adjustment sensors.

Sensor-1 can be adjusted by using the Sensor Offset parameter 06 and Sensor-2 can be adjusted
by using the Sensor Offset parameter 07. Indicates a Sensor of the 

ALFA(NET) 51 

e.g. 2°C to

much, the according Sensor Offset has to be decreased by 2°C.

* Error messages.

In the display of the 

ALFA(NET) 51

 the following error messages can appear:

LO

- Minimum alarm.

Solution E1,E2:

HI

- Maximum alarm.

- Check if the sensor is connected correctly.

E1

- Sensor-1 failure.

- Check sensor  (1000

Ω

 at 25°C).

E2

- Sensor-2 failure.

- Replace sensor.

EEE

- Settings are lost.

Solution EEE:
- Reprogram the settings.

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

  and 

-L-

, as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 

 and 

-H-

, as indication for  a open circuit sensor.

Reset Alarm.

When a error-messages appears it can be resetted by pushing the 

SET

 key. 

The function of this key depends on parameter P37. 

* Technical data.

Type

: ALFA  51 Thermostat or
  ALFANET 51 Thermostat 

Range

: -50/+150,0°C, above -10°C readout per 0,1°C

Supply

: 230Vac 50/60Hz (-5/+10%)

Display

: 3-digit 7-segments display

Relays

: Ry1 = SPST(NO)250V/8A (cos 

φ

=1) or 250V/5A (cos 

φ

=0.4)

  

  Ry2 = SPST(NO)250V/8A (cos 

φ

=1) or 250V/5A (cos 

φ

=0.4)

  Ry3 = SPDT(NO/NC)250V/8A (cos 

φ

=1) or 250V/5A (cos 

φ

=0.4)

    Relays have one common (C)

Control

: By pushbuttons on front.

Front

: Polycarbonate IP65

Sensors

: 2x SM 811/2m (PTC 1KOhm @ 25°C).

Communication

: RS485 Network, 2xTwisted-pair shielded min. 0,5mm

2

 (A,B,Gnd(0V))

Dimensions

: 90 x 71 x 58mm (HWD)

Panel cutout

: 46 x 71mm (HW) for front mounting

Accuracy

: ± 0,5% of the range

- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions are on request available.

* Setting internal parameters.

Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset,
setpoint range and the functions of the thermostat.
Push the 

DOWN

 key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left

display  the  upper-  and  lower-segment  are  blinking.  With  the 

UP

  and 

DOWN

  keys  the  required

parameter can be selected (see the parameter table).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 key to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFA(NET) 51

 changes to the normal operation mode.