* Viewing setpoints.

Viewing setpoint of maximum alarm:

By pushing the 

SET

 key first and then the 

UP

 key together the maximum alarm setpoint

appears in the display. The led 'set high' starts blinking.

Viewing setpoint of minimum alarm:

By  pushing  the 

SET

  key  first  and  then  the 

DOWN

  key  together  the  maximum  alarm

setpoint appears in the display. The led 'set low' starts blinking.

A  few  seconds  after  releasing  the  keys  the  setpoint  disappears  and  the  measured
temperature is shown in the display.

* Changing setpoints.

Push the 

SET

 key together with the 

UP

 or 

DOWN

 key and the maximum alarm setpoint or

minimum alarm setpoint appears in the display. Release both keys.
Now push and hold  the 

SET

 key again and together with the 

UP

 or 

DOWN

 keys the setpoint

can be changed. A few seconds after releasing the keys the measured temperature is shown
again in the display.

* Action of the alarm functions.

The 

ALFA(NET) 23

 alarm thermostat has a minimum alarm and a maximum alarm, both with

there  own  setpoint.  We  can  choose  off  two  different  kind  of  alarms  (PARAMETER  27)
namely:

a watchdog alarm (relay normally activated, at alarm, it falls off and the led 'alarm' burns.
On power failure the alarm relay also falls off.)

or a regulated alarm (relay normally not activated, at alarm, it will be activated and the led

'alarm' burns.

With  PARAMETER  28  we  can  choose  for  a  auto  reset  alarm  or  a  hold  alarm  after
temperature  recovering.  Also  it  is  possible  to  give  both  setpoints  there  own  offset  and
differential, see function diagram.
Each  alarm  can  be  set  at  an  alarm-delay  time  (PARAMETER  23  and  24),  when  the
temperature passes the set alarm point, the led 'alarm' first starts to blink. If the temperature
will recover within the delay time, no alarm occurs. If an alarm will continue after the delay
time, the led 'alarm' burns continuously, and the display alternates between the temperature
and 'H' for high-alarm (max.) or 'L' for low-alarm (min.) to indicate the alarm.
To reset an alarm press the 

SET

 key.

* Setting internal parameters.

Next  to  the  adjustment  of  the  setpoint,  some  other  internal  settings  are  possible,  like
differential, sensor-offset, setpoint range.
By pushing the 

DOWN

 key more than  10  seconds, you enter the 'internal programming

menu'. In the left display the upper and lower segments are blinking. With the 

UP

 and 

DOWN

keys the required parameter can be selected (see table for the parameters). If the required
parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the 

UP

and 

DOWN

 keys, allows you to change the value of this parameter. If after 20 seconds no

key is pushed, the 

ALFA(NET) 23

 changes to it's normal operation mode.

* Parameter ALFA(NET) 23.

Para-
meter

Description Parameter

Range

Standard
Value

02
03
04

Minimum setpoint
Maximum setpoint
Offset temperature sensor

-50/+150

C

-50/+150

C

-15/+15

C

-50

+150

0

10
11

Startup delay after power failure
Relay on at sensor failure

0..99 Minutes
0 = No, 1 = Yes

0
0