* Viewing setpoints.

Viewing set point of maximum alarm:

By pushing the 

SET

 key first and then the 

UP

 key together the maximum alarm set point appears

in the display. The led 'set high' starts blinking.

Viewing set point of minimum alarm:

By  pushing  the 

SET

  key  first  and  then  the 

DOWN

  key  together  the  maximum  alarm  set  point

appears in the display. The led 'set low' starts blinking.

A few seconds after releasing the keys the set point disappears and the measured temperature is
shown in the display.

* Changing set points.

Push the 

SET

 key together with the 

UP

 or 

DOWN

 key and the maximum alarm set point or minimum

alarm set point appears in the display. Release both keys.
Now push and hold  the 

SET

 key again and together with the 

UP

 or 

DOWN

 keys the set point can be

changed. A few seconds after releasing the keys the measured temperature is shown again in the
display.

* Setting internal parameters.

Next to the adjustment of the setpoint, some other internal settings are possible, sensor-offset, relay
function and alarm settings.
By pushing the 

DOWN

 key more than 10 seconds, you enter the 'internal programming menu'. In the

left display the upper and lower segments are blinking. With the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters). If the required parameter is selected, the
value can be read-out by pushing the 

SET

 key. Pushing the 

UP

 and 

DOWN

 keys, allows you to change

the value of this parameter. If after 20 seconds no key is pushed, the 

ALFA(NET) 23 DP

 changes to

it's normal operation mode.

* Parameter ALFA(NET) 23 DP.

Para-
meter

Description Parameter

Range

Standard
Value

04

Offset temperature sensor

-15.0..+15.0

C

0.0

10
11

Startup delay after power failure
Relay on at sensor failure

0..99 Minutes
0 = No, 1 = Yes

0
0

21
22
23
24
25
26
27

28

Differential maximum alarm
Differential minimum alarm
Time delay maximum alarm
Time delay minimum alarm
Offset setpoint High (Max.)
Offset setpoint Low (Min.)
Relay alarm function

(0=watchdog 1=regulated alarm)

Auto reset alarm after temperature recovering 

(0=hold)

0.1..15.0

C

0.1..15.0

C

0..99 Minutes
0..99 Minutes
-10.0/+10.0

C

-10.0/+10.0

C

0 = No, 1 = Yes

0 = No, 1 = Yes

1.0
1.0

0
0

0.0
0.0

0

0

90
95
96
97
98
99

Network number

(Only at ALFANET)

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-