* Setting internal parameters.
To enter the internal parameter menu, use the following instructions;
By pushing the
DOWN
key more than 10 seconds, you enter the ‘internal programming menu’. In the
left display the upper and lower segments are blinking. Over the
UP
and
DOWN
keys the required
parameter can be selected (see table for the parameters). In this case only ‘04’ offset temperature
sensor.
If the required parameter is selected, the value can be read-out by pushing the
SET
key. Pushing the
UP
and
DOWN
keys together with the
SET
key allows you to change the value of this parameter.
If after 20 seconds no key is pushed, the
ALFA(NET) 10
changes to its normal operation mode.
* Parameters ALFA(NET) 10.
PARA-
METER
DESCRIPTION PARAMETER
RANGE
STANDARD
VALUE
04
Offset temperature sensor
-15..+15
C
0
90
95
96
97
98
99
Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)
1..250
0..255
00..99
1..52
0..255
0..999
1
-
-
-
-
-
* Adjustment sensor.
The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the
ALFA(NET) 10
e.g. 2
C too much, the Sensor Offset has to de decreased with 2
C.
* Error messages.
In the display of the
ALFA(NET) 10
the following error messages can appear:
Er
- Sensor broken. Solution:
- Check if the sensor is connected correctly.
- Check the sensor (1000
at 25
C).
- Replace the sensor.
EE
- Settings are lost. Solution:
- Reprogram the settings.