2.1

Installation

On the connection diagram of the Alfanet PC-Interface is shown how the RS485, RS232 or
USB, supply and relays must be connected.
After connecting the Alfanet PC-Interface to the power supply, a self-test function is started,
after this the current time is shown in the display. 

2.2

Control

The Alfanet PC-Interface can be controlled by three pushbuttons. These buttons are:

SET

 

- view / change value of setting.
- changing between real time and % log buffer full on the display

UP

 

- increase value of setting / readout UTC-time.

DOWN

- decrease value of setting.

2.3

Setting internal parameters

For  setting  the  clock,  summer/winter  time  and  the  log-interval  there  are  several  internal
parameters available.
To  enter  the  internal  parameter  menu  the 

DOWN

  key  must  be  pressed  for  more  than  10

seconds.  In  the  left  display  the  upper  and  lower  segment  are  blinking.  Over  the 

UP

  and

DOWN

 keys the required parameter can be selected (see table for the parameters).

If  the  required  parameter is selected, the value can be read-out by pushing the 

SET

 key.

Push the 

UP

 or 

DOWN

 key to change the value of this parameter. 

If 20 seconds no key is pushed, the Alfanet PC-Interface changes to the normal operation
mode and the changes are stored.

Parameters ALFANET PC-INTERFACE.

PARA-
METER

DESCRIPTION PARAMETER

RANGE

DEFAULT

P 01

P 10

P 11
P 12
P 13
P 14

P 15
P 16
P 17
P 18

P 19
P 20

Setting clock 
 (See explanation)
Summer/winter time
 automatic

Month start summertime
Day start summertime
Week start summertime
Time start summertime

Month start wintertime
Day start wintertime
Week start wintertime
Time start wintertime

UTC (Universal Time Coordinated) offset
Log time in UTC

hh:mm yyyy/mm/dd

0=no, 1=yes

1...12 (Jan..Dec)
0...6  (Mo..Su)
1...5

(1e, 2e, 3e, 4e, last)

0...23 (hour) 

1...12 (Jan..Dec)
0...6  (Mo..Su)
1...5

(1e, 2e, 3e, 4e, last)

0...23 (hour) 

-720...+720 Minutes
0=no, 1=yes

-

1

3
6
5
2

10

6
5
3

+60

0

P 30

P 31

P 32

Function Alarm relay
    0 = control alarm
    1 = fail save alarm
    2=  pulse
Function relay 2
    0 = log buffer full
    1 = external alarm NO
    2 = external alarm NC
    3 = external alarm pulse
Detection lost controller

0...2

0...3

0 = no, 1 = yes

0

0

0

P 50

Setting log interval

See explanation

P 90
P 91
P 92

Software version
Serial number
Production date

-
-
-

-
-
-

Summary of Contents for ALFANET PC INTERF.2 RT+MEM

Page 1: ...ut extra memory Hardware user manual Description Alfanet PC interface with real time clock Doc Nr 021865 Type MANUAL Number of pages 12 Version V2 1 File Do021865 Alfanet PC Interface RT USB EM v21 EN...

Page 2: ...2 3 Setting internal parameters 4 3 Program 5 3 1 Installation 5 3 1 1 RS 232 interface 5 3 1 2 USB interface 5 3 2 Control 7 4 Operation of relay outputs 8 5 Front view 9 6 Connections 10 7 Dimensio...

Page 3: ...Buffer full C NO NC 250Vac 10A not inductive Communication RS 485 9600 Baud to ALFANET 2xTwisted pair shielded min 0 5mm2 RS 232 19200 Baud or USB for communication to PC Modem Software PC Software V2...

Page 4: ...he parameters If the required parameter is selected the value can be read out by pushing the SET key Push the UP or DOWN key to change the value of this parameter If 20 seconds no key is pushed the Al...

Page 5: ...0 setting log interval Normally the log intervals are set using the program on the PC It is also possible to set the log interval per network number without the PC Press the SET key once after selecti...

Page 6: ...into the CD player and click on Next The next screen will appear After that the next screen will appear Click on Continue Anyway The software is instead of the message Windows approved The drivers wil...

Page 7: ...p exe If you double click in the file the installation of the Alfanet program will start If the computer can not find the drivers the next screen will appear Click on OK On this screen you choose Brow...

Page 8: ...ergized in normal operation an when an alarm occurs it will be not energized if one of the connected panels on the network has sent an alarm message Pulse means that the relay will be energized for 3...

Page 9: ...ument nr 021865 Version V2 1 Alfanet PC interface 2e gen Client General Page 9 of 12 5 Front view Front view Alfanet PC Interface with RS 232 drawing 020266w4 Frontview Alfanet PC Interface with USB d...

Page 10: ...User manual Document nr 021865 Version V2 1 Alfanet PC interface 2e gen Client General Page 10 of 12 6 Connections Connection diagram Alfanet PC Interface drawing 150474w1...

Page 11: ...User manual Document nr 021865 Version V2 1 Alfanet PC interface 2e gen Client General Page 11 of 12 Connection diagram Alfanet PC Interface drawing 020976w5...

Page 12: ...User manual Document nr 021865 Version V2 1 Alfanet PC interface 2e gen Client General Page 12 of 12 7 Dimensions Dimensions Alfanet PC Interface...

Reviews: