2

* Changing set point.

Push the 

SET

 key and the set point appears in the display. Release the at 

SET

 key.

Now push the 

SET

 key again and together with the 

UP

 or 

DOWN

 keys the set point

can be changed. A few seconds after releasing the keys the measured temperature
shows again in the display.

* Setting internal parameters.

Next  to  the  adjustment  of  the  set  point,  some  internal  settings  are  possible  like
differential, sensor-offset, set point range and the function cooling or heating.
By  pushing  the 

DOWN

  key  more  than  10  seconds,  you  enter  the  'internal

programming menu'. In the left display the upper and lower segment are blinking.
Over the 

UP

 and 

DOWN

 keys the required parameter can be selected (see table for

the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

key. Pushing the 

UP

 or 

DOWN

 keys together with the 

SET

 key allows you to change

the value of this parameter.
If after 20 seconds no key is pushed, the 

ALFA 11

 changes to it's normal operation

mode.

* Adjustment sensor.

The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates
the 

ALFA 11

 e.g. 2

C too much, the Sensor Offset has to de decreased with 2

C.

* Error messages.

In the display of the 

ALFA 11

 the following error messages can appear:

Er

- Sensor broken.  Solution:

- Check if the sensor is connected correctly.
- Check the sensor (1000

 at 25

C).

- Replace the sensor.

EE

- Settings are lost.  Solution:

- Reprogram the settings.