Air Differential Pressure Transmitters
with 0-10 Vdc or 4-20 mA Output

984M-
series

Pressure range

low

high

Response

slow

fast

Mode

linear

*square root

Output signal

0-10 Vdc

4-20 mA

Pressure range

low

high

Response

slow

fast

Mode

linear

*square root

Offset Calibration

This function can be used to correct the zero-point deviation (offset) of the output signal in
depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.

Then press the “M” button for 5 s.

M = Mode

Offset Calibration

This function can be used to correct the zero-point deviation (offset)
of the output signal in depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.
Then follow the programming instructions on the next page.

Setting of Switching Output

This function is used to set the switching output to “switched through” for a pressure you have defined.
The LED lights up as soon as the defined pressure is reached or exceeded.

Peak Value

The shown low/high peak value is the value that was ever set at the sensor.

A resetting of the peak value can take place only at the manufacturer.

M = Mode

S = SET

LED

Offset Calibration

This function can be used to correct the zero-point deviation (offset)
of the output signal in depressurised state (example: to 0 V/4mA at zero Pa).
Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses.
Then press the “M” button for 5 s.

Setting of Switching Output

This function is used to set the switching output to “switched through” for a pressure you have defined.
Apply the pressure or pressure differential at which the switching output is to be connected.
Then press the “S” button for 5 s until the LED flashes quickly (= value is saved).

The LED lights up as soon as the defined pressure is reached or exceeded.

Pressure range

low

high

Response

slow

fast

Mode

linear

*square root

Output signal

0-10 Vdc

4-20 mA

Switches and jumper settings

984M.3x3104,

 0-10 Vdc/4-20 mA without LED display

984M.3x3114,

 0-10 Vdc/4-20 mA with LED display

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

984M.3x3204,

 4-20 mA

*Square root = 984M can be used for volume flow measurement, this product feature is at extra cost and have to be requested when ordering.

switched

open

switched

open

switched

open

M = Mode

S = SET

LED

Error messages

sensor
defect

measurement
exceeding