background image

 

Form V372, Rev. 12 

- 3 - 

12/18, ECN4334 

 

SECTION 2: DESCRIPTION OF THE VAUGHAN 

ROTAMIX™ SYSTEM 

The Vaughan Rotamix™ system is a proprietary (patent 7,025,492) mixing system designed to mix 
cylindrical, egg-shaped, or rectangular sludge storage tanks or digesters with greater mixing efficiency 
and lower power requirements than some other systems that have been traditionally used. 
 

The Rotamix™ system consists of one or more Vaughan chopper pumps pumping through a customer-
supplied piping system to one or more Vaughan-supplied nozzle assemblies. 
The glass-lined ductile iron nozzle assemblies are typically floor-mounted, dual-nozzle systems, but can 
also be single nozzle systems (generally in rectangular tanks). In a cylindrical storage tank and with 
dual nozzle assemblies, the lower nozzle is aimed more toward the center of the tank, while the upper 
nozzle is aimed to create more tangential rotation. 

Nozzle aiming must be done per Vaughan 

instructions once nozzle assembly installation is complete but before the storage tank is closed up.

 

Please contact your local representative for aiming the nozzles. Nozzles normally cannot be aimed 
remotely on floor-mounted systems. 
 

A layout drawing of the Rotamix™ system (showing nozzle location and nozzle angles within the tank) 
is included in your custom Installation, Operation and Maintenance Manual package for your particular 
project. 

SECTION 3: INSTALLATION INSTRUCTIONS 

A.  RECEIPT INSPECTION 

Description of pump receipt inspection is described in the IO&M Manual for the Vaughan chopper 

pump. You should also inspect the nozzle assemblies received for the Rotamix™ system to make sure 
they have arrived undamaged. Your best indication of potential shipping damage to equipment is the 
condition of the crating. If the crating is damaged, look for cracked fittings and clamps or damaged 
paint, 

report damage to your carrier.

 Vaughan Co. can also work with you to provide replacement 

fittings as needed. 

B. STORAGE CONSIDERATIONS 

The epoxy paint on the nozzle assembly is susceptible to damage from prolonged UV exposure. If 
nozzle assemblies are to be stored for more than two weeks prior to installation they must be either 
stored indoors or covered. If nozzle assemblies will be exposed to sunlight for more than two weeks 
after installation they should be covered. 

C. INSTALLATION 

The Vaughan chopper pump is to be installed as described in the pump IO&M Manual. Note however, 
that the Rotamix

TM

 system reason for being is to achieve improved efficiency over your previous mixing 

systems. Therefore the Rotamix

TM

 system piping design should minimize friction losses through the 

suction and discharge piping. This means using suction and discharge piping dimensions as shown on 
your system outline drawing. 

For best results choose piping size so that velocity is around 3-5 ft/sec. for suction piping and no more 
than 8 ft/sec for discharge piping. This is fast enough to avoid particle settling in the piping, but slow 
enough to minimize friction losses. Vaughan Co. will help you with your system design. Please consult 
us to be sure your system works as intended.  

 

Use of smaller diameter piping than recommended results in higher velocities, increased friction 
loss, and less effective tank mixing. 

Smaller diameter piping may lead to troublesome gas-binding problems in the mix pump because of 
decreased pressure at the pump suction that tends to liberate volatile gases from the pumped fluid. 
Gas binding in the pump can result in complete loss of flow and low motor amps. If the pump is gas 
bound, even though the pump is turning, no mixing will be taking place. To restore flow stop the pump 
and vent all the trapped gas out of the pump casing before restarting the pump. 

Summary of Contents for ROTAMIX SYSTEM

Page 1: ...STALLATION OPERATION MAINTENANCE INSTRUCTIONS VAUGHAN CO INC 364 Monte Elma Road Montesano WA 98563 Phone 1 360 249 4042 Fax 1 360 249 6155 Toll Free Phone US only 1 888 249 CHOP 2467 Web Site www chopperpumps com Company E mail info chopperpumps com ...

Page 2: ...Form V372 Rev 12 10 18 ECN4334 This manual is for all Vaughan Rotamix Systems NOTE The pump for your Rotamix System will require an additional IO M manual ...

Page 3: ... A Receipt Inspection B Storage Considerations C Installation I Vaughan Foambuster II Roof Mounted Nozzles III System Venting D Nozzle Aiming Instructions 4 STARTUP INSTRUCTIONS Page 7 5 NORMAL OPERATION Page 12 A Digester Mixing B Sludge Tank Mixing C Blend Tank Mixing 7 SHUTDOWN INSTRUCTIONS Page 13 8 MAINTENANCE Page 13 A Routine Maintenance B Corrective Maintenance 9 TROUBLESHOOTING Page 14 10...

Page 4: ...of low voltage poor ventilation overloaded lines etc These motors can restart automatically as the motor cools down DO NOT work on the pump or motor without first disconnecting and locking out the power supply Enter tanks or pits with extreme caution and only after an instrument check of the pit tank has been completed to verify the absence of dangerous gases and the presence of safe levels of oxy...

Page 5: ...wn from the pump as a projectile All pumps must be run with suction and discharge piping in place or blind flanges installed on suction and discharge connections Blind flanges should be vented to avoid pressure build up Note that cast rotating parts could break if metal to metal contact occurs while the pump is running dry Shut pump off when adjusting fittings to avoid being sprayed with pumpage P...

Page 6: ... the crating is damaged look for cracked fittings and clamps or damaged paint report damage to your carrier Vaughan Co can also work with you to provide replacement fittings as needed B STORAGE CONSIDERATIONS The epoxy paint on the nozzle assembly is susceptible to damage from prolonged UV exposure If nozzle assemblies are to be stored for more than two weeks prior to installation they must be eit...

Page 7: ...ming particularly in activated sludge plants The Foambuster nozzle must be mounted above liquid level Only a few inches of distance is enough to allow the Foambuster to work Also the Foambuster needs about 4 ft of headroom above the height of the nozzle to allow the spray to cover as much of the tank surface as possible The Foambuster works best with a fixed cover Finally the Foambuster is designe...

Page 8: ...st approach b You can use a solenoid controlled valve 2 is best controlled by a timer in your control panel which would open this valve prior to each startup of the pump Based on experimentation you can determine how long it takes to vent the gas from the system to completely fill the pump casing before the pump starts You can then set the timer to this setting Again run the piping either to a dra...

Page 9: ...egree mark on the protractor See your Nozzle Layout drawing for the proper angles to set your nozzles Moving the lower nozzle will tend to move the protractor also Be sure to recheck the zero point before tightening the lower nozzle clamp STEP 4 To aim the upper nozzle tie the plumb bob string to the bolt on the nozzle clamp as shown Make sure that it hangs from the the center of the nozzle Loosen...

Page 10: ...o mixing at allSee the pump IO M Manual for pump startup and operating instructions Vaughan Co requires the Startup Certification Checklist pages with the job specific Vaughan Rotamix tank drawing marked up with nozzle locations nozzle angles nozzle elevations and confirmation of all bolt torques to be sent to Vaughan Engineering If the job specific tank drawing is not available please contact Vau...

Page 11: ...rmation of all bolt torques to be sent to Vaughan Engineering All verified dimensions should be indicated by a circle or check mark on that dimension Rotamix Drawing No _____________________________ Is drawing attached Yes ____ No ____ Is drawing marked up to show each verified nozzle location Yes ____ No ____ Is drawing marked up to show each verified nozzle angle Yes ____ No ____ SYSTEM DATA Tan...

Page 12: ..._____ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ___________________...

Page 13: ...f maintaining continuous mixing during foaming or RVE events is that pockets of feed sludge are continuously mixed with the rest of the digestate spreading out gas generation over a maximum time period to minimize sudden bursts of liberated gas By maintaining continuous mixing at lower speeds the gas generation and therefore the foam generation is kept more under control Reduced energy mixing for ...

Page 14: ...working order and that the nozzles are still properly aimed Whenever you check the nozzle system inspect the nozzle opening to make sure that the glass coating is still intact If the glass coating and ductile iron metal is worn away replace the nozzle For polyurethane nozzles measure the discharge diameter to make sure that it is no more than 15 larger than it was when new For example a new 2 00 d...

Page 15: ...ump speed For example if 100 speed is at 60 Hz on your VFD do not run the VFD at less than 45 Hz Too slow of a speed reduces pump and system pressure and can result in nozzle plugging 2 Troubleshooting the nozzles A Historically about of 1 of Rotamix systems experience a plugged nozzle so while blockage can occur it s not a common problem Nozzle blockage may show up as reduced mixing within your d...

Page 16: ...sentatives is required and can head off problems with installation of incorrect nozzle size D A worn nozzle may show up as increased mixing within your digester or storage tank Other symptoms of a worn nozzle could be higher than normal mixing pump electric motor power requirements higher amps and lower pump discharge pressure compared to your recorded readings at startup You may also hear pump ca...

Page 17: ... VSR and this means that more gases of decomposition methane and carbon dioxide are generated We want high VSR for better digestion and we want more gas for cogeneration of electricity However generating too much gas in a digester over too little time can lead to foaming RVE issues and possible digester overflows Digester overflow means bad odors a big cleanup and complaints from residential neigh...

Page 18: ... start If foaming occurs after startup of the mixing system and a Foambuster has not been installed with the system the recovery costs for installing a Foambuster are much higher D Poor mixing can result if the viscosity of the mixed sludge is too high This situation can occur when mixing very thick TWAS thickened waste activated sludge Once TWAS gets up to the range of 6 7 solids mixing may be di...

Page 19: ...le parts are repaired or replaced by anyone other than Vaughan Co or its duly authorized representatives Vaughan Co assumes no liability for consequential damages of any kind and the purchaser by acceptance of delivery assumes all liability for the consequences of the use or misuse of Vaughan Co products by the purchaser its employees or others Vaughan Co will not be held responsible for travel ex...

Reviews: