19
Below table shows the permitted layers in a specific direction:
Direction
Maximal Layers
Comments
Z1
3 layers
To avoid too much weight
Y1
1 layer
To ensure proper ventilation
Z2
5 layers
To avoid too much weight
Y2
1 layer
To ensure proper ventilation
Z3
3 layers
To avoid too much weight
7.2
Electrical connection
It is not allowed to connect the modules in series! Only connect the battery modules in parallel.
Do not mix up 24V and 48V battery modules within a single system.
The next steps describe how to connect the battery modules in parallel.
Step 1: Minus terminal
Connect the Power Minus of all modules in parallel. Tighten it with a torque of max 3.9 Nm. Please
note the Power minus is marked with the symbol -. For connection of the modules an additional bus
bar or a wires with cable lug is needed.
Step 2: Plus terminal
Connect the Power Plus of all modules in parallel. Tighten it with a torque of max 9 Nm. Please note
the Power Plus is marked with the . For connection of the modules an additional bus bar or a
wires with cable lug is needed.