![Varmeteknikk MB 35 Installation, Operation & Service Manual Download Page 8](http://html2.mh-extra.com/html/varmeteknikk/mb-35/mb-35_installation-operation-and-service-manual_3558741008.webp)
Varmeteknikk AS
August 2017 e-mail: [email protected]
8
Error temp:
Temperature sensor is broken
Alarm net:
Control voltage < 190V
Alarm power:
Power supply missing*
*
Alarm power
is activated if controller when reaching step 3, doesn’t measure any power. The
reason for this could be that main switch/circuit breaker on the switch board is OFF, security
temp. limiter (STB) released because of high temperature, heating element/fuse is broken, or
contactor is not connected.
Settings
Failure Menu button Enter button
Preset temperature:
Temperature range is from 30 – 95 °C. Preset temperature is factory set to 80 °
C
. If correction is
needed do the following:
Press
+
or
–
button to set desired temperature. Then press enter to save new value.
Step time:
Step time is adjustable between 20-250 sec. (factory setting is 40 sec.) and refer to connection of
power steps. When disconnecting power, step time is 5 sec. with step time below 60 sec., 10 sec
with step time above 60 sec. If correction is required do the following: Press menu button once to
enter step limitation mode. Then press
+
or
–
button. To enter step time mode press menu button.
With +/- button choose desired step time. Press
E
button to save new value.
Step 0( 7)
Step time 40s
►
Step lim 0( 7)
Step time 40s
Step lim 0( 7)
Step time 40s
►
Step 0( 7)
Step time 50s
To return to temp/power mode, press menu button.
Summary of Contents for MB 35
Page 1: ...Installation operating servicing MB boilers 35 45 60 75 90 105 120 140 150kW...
Page 15: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 15 Circuit diagram MB 35 150kW...
Page 17: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 17 Temp controller terminals...
Page 18: ......
Page 20: ......
Page 21: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 21 Notes...