Parallell and inclination adjustment
If the set temperature that the controller calculates is too high or low, the curve "parallel" can be
shifted up or down. By pressing the menu button twice, the display shows:
Outdoor t. -15°C
Parallel 0°C
With the «+/-» buttons the curve can be set between -20 and +20. New value must be saved by
pressing "E" button. If the travel temperature is not high enough on cold days, the inclination curve
can also be adjusted. By choosing a steeper curve, the trip temperature can be further increased.
Adjustment of the slope is made in the service menu, see page 12. In the menu «slope» the
desired curve is set with the «+/-» buttons. New value is saved by pressing the «E» button.
Curve 40°C
Curve min 60°C
With the «+/-» buttons the slope can be set between 22 and 60. New value must be saved by
pressing «E» button. With Slope min, you can set a minimum limit of how low you want to allow the
temperature to drop.
See an overview of the menus on page 11.