MiniVap
Positioning the MiniVap Unit
DOs
DO mount the unit indoors.
DO mount the unit close to the steam nozzle / steam pipe
position.
DO ensure adequate service access to the front of the unit
(min 700mm).
DO remove the cylinder, if necessary, to access the mounting
holes in the back of the steam section.
DO use M6 projecting type wall bolts or equivalent fixings to
mount the unit in position.
DO mount unit with a Room Distribution Unit (RDU) so that the
steam discharge is above head height. (An RDU includes a
steam nozzle and a small fan with 230Vac motor.)
DON’Ts
DON’T mount the unit outside.
DON’T install the unit close to sources of strong electro-
magnetic emissions eg variable speed lift motor drives, KVA
transformers, etc.
DON’T mount unit in an unventilated enclosure.
DON’T mount in a position requiring ladder access to the unit.
DON’T install the unit behind a false ceiling or other situation
where an unusual malfunction (eg water leak) would cause
damage.
DON’T install the unit in an area which will be hosed down.
DON’T install the unit where the ambient air temperature can
exceed 35°C.
DON’T mount the unit inside a cold-room or other place where
temperature and humidity conditions can cause condensation
on electrical components.
DON’T mount the unit where the sound of a contactor opening
/ closing and water flow in a pipe would be unacceptable eg
libraries, private apartments, etc.