Electrical Connections

Important  E.M.C. Considerations

Use a dedicated, earthed metal conduit for both the
control signal cable and the security circuit cables
along their entire length - they may share the same
conduit where practicable.  The earth must be made
by "metal-to-metal" contact and should be a good
RF (Radio Frequency) earth.

The control and security circuit connections should
be run in screened cable with the screen grounded
at the Microvap end (onto the electrical section back
panel).  The screen should be maintained as close
as possible to the cable ends and any tail between
the screen and the earth point must be kept short
(50 mm maximum).

Control Cable / Security Circuit
Conduit Entry Arrangement

Control Cable / Security Circuit

Screening Arrangement

Tail to be kept short
(less than 50mm)

Cables to control terminals

     Screen  left intact

Outer insulation

      Earthed back panel

Important Power Connection Information

Vapac 24V secondary Transformer Primary supply connections:
Vapac units are wired to allow connection to alternative site Voltages.
Make the following simple checks before connecting the power supply:-
Move the RED connection on the  Microvap transformer primary winding
circuit to the position marked with  the supply Voltage that is to be connected
between Microvap power terminals A1 and A2.
The transformer primary circuit terminal positions are clearly marked:- 200V,
230V, 380, 415 & 440V. For sites where the actual (measured) voltage is
400V the preferred transformer tapping is 380V.

Note:

24 V a.c. Control circuit

    - 

Transformer Primary Circuit   -
And RDU.

230V ac Pump Supply.

    -

3.15 A  20 mm (F - Quick blow) fuse  (Pt.No. 1080096) mounted on Terminal
rail F3 for master control and F4 for slave unit control.

Two fuses protect the control circuit on Single cylinder units F1 2.0A (slow
blow) (Pt. No. 1080095) mounted in fuse-terminal holder protects Primary
transformer and RDU unit if fitted. F2 500 mA 20 mm  (F - Quick blow) fuse (Pt
No. 1080054) mounted in fuse-terminal holder protects Transformer Primary
and Pump or both pumps if two pumps are fitted. Twin cylinder units F5 2.0A
(slow blow) (Pt. No. 1080095) mounted in fuse-terminal holder protects second
RDU unit if fitted.

The pump or pumps on twin cylinder units are feed from the main transformer
via a 230 volt auto winding. The pumps are protected by fuse F1 and F2 above
feeding the transformer primary.

All metal surfaces which come
into contact with each other,
must be free of paint, grease,
dirt, etc., thereby ensuring a
good low impedance R.F.
(Radio Frequency) path to
ground.

Electrical section metalwork

Metal conduit

Summary of Contents for MICROVAP V15

Page 1: ... Directives This product will meet the requirements of the Low Voltage Safety Directive 73 23 EEC and the EMC Directive 89 336 EEC when installed in accordance with the instructions contained in this manual Failure to comply with these instructions may invalidate the manufacturer s warranty or any certificate declaration of conformance requested to be supplied with the unit ...

Page 2: ...rvice or exchange hazardous Make sure steam line s have adequate slope min 12 for condensate drainage and use condensate separators if the pipe is lower than the unit Provide adequate support to prevent sags developing in flexible steam lines which can fill with water and create a trap Do not locate vented drain directly under the cabinet Important Electrical Connection Items Before commissioning ...

Page 3: ...on t mount in a position requiring ladder access to the unit Don t mount the unit behind a false ceiling or other situation where an unusual malfunction e g water leak would cause damage Don t mount the unit in an area which will be hosed down Don t install the unit where the ambient temperature can exceed 35oC Don t mount the unit inside a cold room or other place where temperature and humidity c...

Page 4: ...eam pipes horizontal mounted must discharge vertically upward Notes Con t 4 Vertical mounted steam pipe must discharge horizontally facing upstream airflow 5 If the total pressure within the duct air flow exceeds 2000 Pa and the static pressure is below 2000 Pa then the probe may face horizontally at right angles to the air stream Key 1 Insulated Steam Pipe 2 Steam Distribution Pipe 3 Hose clip 4 ...

Page 5: ... to a condensate separator Always provide a continuous slope Do provide adequate support to prevent sagging a fit pipe clips every 30 50cm or b support straight lengths on cable trays or in heat resistant plastic pipe Do ensure radius hose bends are fully supported to prevent kinks developing when in service Do add extra insulation to steam hose for longer runs 2m 5m and in cold ambient conditions...

Page 6: ...ically close to the unit a ground earth stud is positioned on the underside of the cabinet Drain capacity per cylinder pump discharge rate of max 16 8 l min at 50 Hz Power supply 17 2 l min at 60 Hz Do s Do use copper or plastic pipe rated for 100 oC Do arrange to discharge drain water from the unit into a trapped and vented drain at a position where flash steam rising from the drain line vent wil...

Page 7: ... winding circuit to the position marked with the supply Voltage that is to be connected between Microvap power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked 200V 230V 380 415 440V For sites where the actual measured voltage is 400V the preferred transformer tapping is 380V Note 24 V a c Control circuit Transformer Primary Circuit And RDU 230V ac Pump Sup...

Page 8: ...200V 230 380 415 and 440V and requires on site adjustment to match it to the Voltage connected to Vapac terminals A1 and A2 The transformer 8V secondary supply is not used Important The Vapac transformer must NOT be used to power other equipment or the warranty will be invalidated RDU Connection Vapac terminals 25 26 and 27 28 are included to provide a 230Vac electrical supply for the fan motor in...

Page 9: ...9 ...