CHECKING GAS CONNECTIONS
WARNING: Test all gas pip
-
ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor
-
rect all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak
detection fluid to all joints.
Bubbles forming show a leak.
Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
fireplace. See guidelines under
Connecting Fireplace to Gas
Supply
, page 15.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace with its main gas
valve (control valve) and equipment shut
-
off valve from gas supply piping system.
Pressures in excess of 1/2 psig will dam-
age fireplace regulator.
2. Cap off open end of gas pipe where equip
-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment
shutoff valve to gas supply. Check recon-
nected fittings for leaks.
INSTALLATION
Continued
Figure 18 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff Valve
Figure 20 - Checking Gas Joints for
Propane/LP Gas
Propane/LP
Supply Tank
Equipment
Shutoff
Valve
Gas Control Valve
Gas Meter
Figure 19 - Checking Gas Joints for
Natural Gas
Gas Control Valve
Equipment Shutoff Valve
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see
Figure 18).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter to equip
-
ment shutoff valve for natural gas or pro-
pane/LP supply to equipment shutoff valve
for propane/LP (see Figures 19 and 20).
Apply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
4. Correct all leaks at once.