b.

 

Address conflicts can be identified by an orange box 
in the table. Alternatively, if an address conflict is 
suspected even if an orange address box is not seen, 
click on the green address box where the suspected 
conflict exists, which will turn on all loads assigned to 
that address. If the conflict is verified doing this, drag 
the green (or orange) address box to the 

Remove 

Address

 button at the top of the table. This will 

momentarily remove the loads from the table at that 
address, (the address box goes gray). Click the search 
button should to rediscover each of those loads 
individually and reassign them to the lowest available 
unique address. Example, if there were 30 loads 
assigned to A0, dragging A0 to 

Remove Address

 then 

clicking search should populate the table with green 
address boxes on addresses A0-A29. 

 

 

BUS Manager TIPS (DALI)

 

Because the Vantage system controls load levels and fade time 
it is recommended that all DALI loads have these parameters 
set to default. If a DALI load appears to have light level issues 
and or fade time issues, use the 

Config Devices

 option in the 

BUS Manager

 tool to reset these load parameters to factory 

levels as illustrated here.  

 

Select a load in the 

Address 

Devices

 screen and click the 

green box address to turn 
the load on. 

 

Change to page in the BUS 3 
manager to the 

Config 

Devices

 page and then click 

the 

Factory Default

 button. 

 

Change the Config Devices 
page back to RUN Gateway 
and then exit the BUS 
Manager tool. 

 

The load should now work 
using default light levels and 
fade times.  

 
 
Steps to Update Station Firmware 

Close communication between the DDG station and any 
connected devices by pressing the Reset button. 

 

Press and release the reset button – do not hold it in 

o

 

The DDG station reboots into boot loader mode, LEDs 
may flicker and then go off 

o

 

The station is now ready for the new firmware to be 
downloaded. 

 

Download the firmware update 
file from the Vantage dealer site. 
The file name should be similar 
to: 

DGM01_FW_2_99_VANTAGE.HTM
L.

 

 

The computer and DDG station 
must be on the same network. 

 

Double click on the downloaded 
HTML file to open the internet 
firmware updater window. 

 

Enter the DDG station IP address, 
step 

2)

 in illustration above. 

 

Click the Update button, step 

3)

 

in illustration above right. 

 

When the update is complete a 
message similar to the one at the 
right should open.  

 

Cycle power to the DDG station 
to reboot the station out of boot 
loader mode. 

 

Firmware update is complete. 

 
Trouble Shooting, General Information & Tips 

 

Equinox Devices

 – If all 512 loads are created in Design 

Center it is recommended to select the 

Exclude From 

Widgets

 box all loads not wanted in the 

Equinox Lighting 

Widget

.  

 

DALI Scan Time (DALI Bus 3) 

– The DALI default scan time 

is set to 25ms. This may not be long enough for some load 
types. Increase the scan time until all lights respond 
correctly.  Scan  times  may  be  as  high  as  500ms  or  even  1 
second, etc. The DALI scan time is set in the 

DGM 

Configuration

 tool. 

 

Light levels are restored after a power outage. 

 

When controlling DMX and DALI on the same DDG station, 
it is important to know that the practice of overlapping 
DMX and DALI channels is not recommended. Overlapping 
channels may cause unwanted ramp/fade cycles when 
different devices share the same channel. 

 

After a full system program, communication between the 
station and the InFusion Controller takes about 90 seconds. 
If communication does not begin –  

o

 

double check the IP address entered in Design Center, 

o

 

cycle power to the DDG station and re-program the 
system from Design Center, 

 

 

 