Vanguard VDVF36PN Owner'S Operation And Installation Manual Download Page 12

12

105706

DIRECT-VENT GAS FIREPLACE HEATER

VDVF36P and VDVF36ST Series

®

4.

Connect a section of pipe and extend
up through the hole.

Note:

 If an offset is needed to avoid

obstructions, you must support the vent
pipe every 3 feet. Use wall straps for
this purpose (see Figure 24). Whenever
possible, use 45

°

 elbows instead of 90

°

elbows. The 45

°

 elbow offers less re-

striction to the flow of the flue gases
and intake air.

5.

Place the flashing over the pipe
section(s) extending through the roof.
Secure the base of the flashing to the
roof and framing with roofing nails. Be
sure roofing material overlaps the top
edge of the flashing as shown in Figure
24. There must be a 1" clearance from
the vent pipe to combustible materials.

6.

Continue to add pipe sections until the
height of the vent cap meets the mini-
mum building code requirements de-
scribed in Figure 13 on page 6.

 Note

: You

must increase vent height for steep roof
pitches. Nearby trees, adjoining rooflines,
steep pitched roofs, and other similar fac-
tors may cause poor draft or down-draft-
ing in high winds. Increasing the vent
height may solve this problem.

7.

Twist-lock the vent cap onto the last
section of vent pipe and seal with high
temperature silicone sealant as speci-
fied in the second warning statement
on page 7.

Note:

 If the vent pipe passes through any

occupied areas above the first floor, including
storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclo-
sure with standard construction material. Make
sure and meet the minimum allowable clear-
ances to combustibles. Do not fill any of the
required air spaces with insulation.

Cathedral Ceiling Installation

1.

Remove shingles or other roof cover-
ing as necessary to cut the rectangular
hole for the support box. Mark the out-
line of the cathedral ceiling support box
on the roof sheathing using the locat-
ing hole as a center point.

2.

Cut the hole 1/8" larger than the sup-
port box outline (see Figure 26, page 13).

1.

Determine the route your vertical vent-
ing will take. If ceiling joists, roof
rafters, or other framing will obstruct
the venting system, consider an offset
(see Figure 24) to avoid cutting
loadbearing members. 

Note:

 Pay spe-

cial attention to these installation in-
structions for required clearances (air
space) to combustibles when passing
through ceilings, walls, roofs, enclo-
sures, attic rafters, etc. Do not pack air
spaces with insulation. Also note maxi-
mum vertical rise of the venting sys-
tem and any maximum horizontal off-
set limitations. Offsets must fall within
the parameters shown in Figure 13 on
page 6.

2.

Set the fireplace in desired location.
Drop a plumb line down from the ceil-
ing to the position of the fireplace exit
flue. Mark the center point where the
vent will penetrate the ceiling. Drill a
small locating hole at this point.

Drop a plumb line from the inside of
the roof to the locating hole in the ceil-
ing. Mark the center point where the
vent will penetrate the roof. Drill a
small locating hole at this point.

Flat Ceiling Installation

1.

Cut a 10" square hole in the ceiling us-
ing the locating hole as a center point.
The opening should be framed to
10"x10" (254mm x 254mm) inside di-
mensions, as shown in Figure 17 on
page 9 using framing lumber the same
size as the ceiling joists. If the area
above the ceiling is an insulated ceil-
ing or a room, nail firestop from the
top side. This prevents loose insulation
from falling into the required clearance
space. Otherwise, install firestop below
the framed hole. The firestop should be
installed with no less than three nails
per side (see Figure 25).

2.

Assemble the desired lengths of pipe
and elbows necessary to reach from the
fireplace flue up through the firestop.
All connections must be sealed with
high temperature silicone sealant as
specified in the second warning state-
ment on page 7. Be sure all pipe and
elbow connections are fully twist-
locked (see Figure 16, page 9).

3.

Cut a hole in the roof using the locating
hole as a center point. (Cover any ex-
posed open vent pipes before cutting
hole in roof.) The 10"x10" hole must
be measured on the horizontal; actual
length may be larger depending on the
pitch of the roof. There must be a 1"
clearance from the vent pipe to combus-
tible materials. Frame the opening as
shown in Figure 17 on page 9.

VENTING
INSTALLATION

Continued

Figure 24 - Offset with Wall Strap and 45

°

45

°

 Elbow

Wall Strap

Roof
Flashing

Ceiling Firestop

Figure 25 - Installing Firestop

If area above is not a room, install
firestop below framed hole.

If area above is a room, install firestop
above framed hole.

INSTALLATION FOR
VERTICAL TERMINATION

NOTICE: Use rigid pipe only. Flex
venting is not to be used with a
vertical termination.

Summary of Contents for VDVF36PN

Page 1: ...s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier SAVE THIS BOOK This...

Page 2: ...sions Back of Surround Back of Surround Figure 2 VDVF36STN STP See Thru Dimensions Left Side Surround Right Side Surround Rating Plate Location Left Side Surround Right Side Surround GLOSSARY OF TERMS...

Page 3: ...han the type of gas approved for use in this gas appliance NOTICE Check local building codes for area requirements be fore installing this appliance This appliance when installed must be elec trically...

Page 4: ...UTION Do not block re quired air spaces with insula tion or any other material Do not obstruct the effective opening of the appliance with any type of facing material MANTEL CLEARANCES Woodwork such a...

Page 5: ...maxi mum thickness of 3 4 Do not recess venting terminals into a wall or siding Install horizontal venting with a 1 4 rise for every 12 of run toward the ter mination You may paint the vent terminal...

Page 6: ...ve paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum...

Page 7: ...t the proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizo...

Page 8: ...s to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lugs will slide s...

Page 9: ...utside edge of the vent cap Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is...

Page 10: ...rtical V and Horizontal H maxi mums and minimums The same amounts apply for flexible venting FGFVK Vent Kit Shown Horizontal Termination Configurations Figures 21 through 23 show different con figurat...

Page 11: ...90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 4 max 6 min 8 max 7 min 10 max 8 min 15 max 20 max 20 max Figure 23 Horizontal Termination Configuration for Rigid Venting Using Two 90 Elbows w...

Page 12: ...nces air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do not pack air spaces with insulation Also note maxi mum vertical rise of the venting sys tem an...

Page 13: ...ort box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the supportbox from the top corne...

Page 14: ...guration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 20 ma...

Page 15: ...12 Firestop Support Roof Flashing RTV Silicone Vertical Termination and 26 screws D1000 7 x 12 Galvanized Coaxial Pipe 6 pcs D1010 7 x 24 Galvanized Coaxial Pipe 6 pcs D1020 7 x 48 Galvanized Coaxial...

Page 16: ...erly connected to a standard 120 VAC power source Refer to Wiring Diagram on page 23 An outlet box with two receptacles has been supplied for your convenience located on the lower left side of the app...

Page 17: ...sig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its indi vidual manual shut off valve during any pressure testing of the gas supply piping system at test pressu...

Page 18: ...is section is intended as a guide for qualified service technicians installing gas to the appliance CAUTION Do not connect appliance before pressure test ing gas piping Damage to the gas valve may res...

Page 19: ...roofed is not considered noncombustible Left Right Back Front Left Front Right Back B B A A Figure 44 Installing Logs A Top View Figure45 InstallingLogs B TopView PILOT ASSEMBLY ADJUSTMENT The pilot a...

Page 20: ...proper safety gloves to re move the broken glass door Dis card safely A glass door kit can be ordered through your local distributor Do not substitute other material for the glass WARNING Children an...

Page 21: ...all electrical power to the appliance 4 Open control access panel 5 Push in gas control knob slightly and turn clockwise to OFF 6 Wait five 5 minutes to clear out any gas Then smell for gas including...

Page 22: ...ineered to take an air temperature sample ev ery 5 5 minutes in the auto mode It will not respond immediately to the temperature setting being turned up or down IMPORTANT The hand held re mote control...

Page 23: ...ilot will not stay lit burner will produce flames and soot fireplace will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so contact your local propane LP gas supplier WIRI...

Page 24: ...ing to light the fireplace 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier 5 Refer to section on pilot lighting 6 Have a qualified technician rep...

Page 25: ...6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut i...

Page 26: ...rner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Clean burner or replace burner orifice 1 Adjust the log set so that the flame does not excessively impinge...

Page 27: ...ent cap installation 1 Gas leak See Warning statement above 2 Control valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame...

Page 28: ...KIT 105742 01 22180 Wall Switch 105902 01 14112 Cover Plate 105903 01 14113 Wallswitch coverplate andmillivoltwires are supplied with the appliance If wires need replacing use proper gauge Millivolt...

Page 29: ...105890 02 25238 REFRACTORY PIECES Front Bottom 105886 01 25854 Left Right Bottom 105887 01 25856 Rear 105888 01 25855 BURNER ASSEMBLY 105885 01 27243 REPLACEMENT PARTS Continued Front Bottom Left Rig...

Page 30: ...e the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES A...

Reviews: